If the available documentation is not sufficient for solving the problem, contact Marelli Motori
Service for further instructions.
All operations indicated below are to be performed with the machine off, except where
specifically noted.
PROBLEM
With
the
generator
started, with no-load, the
voltage to the output
terminals is less than the
nominal value and equal
to the residual voltage of
the machine; this value
remains
even
after
having
adjusted
the
VOLT
and
VFINE
potentiometers.
Once the blown fuse is
replaced, there is again
a fuse interruption.
963857154_U
POSSIBLE CAUSE
There
is
no
connection
regulator power terminals P1 and P2 and
(according to the application):
the auxiliary winding
the
main
generator
terminals
the PMG output
There is no connections between the +
and - terminals on the regulator and the
exciter field.
Terminals P and Q have no jumper or
are
not
connected
potentiometer.
Regulator powered by auxiliary winding:
the residual voltage of the auxiliary is
insufficient for self-excitation (minimum
voltage required, 5V).
Regulator powered from main terminals:
the residual generator voltage between
P1 and P2 is insufficient for self-
excitation (minimum voltage required,
5V).
Regulator powered from the PMG: the
PMG output voltage and P1 and P2 input
voltage is insufficient for self-excitation
(minimum voltage required, 5V).
Internal fuse interrupted
Regulator failure.
Regulator failure.
OPERATION
between
Check
diagram provided with the generator).
output
Check
diagram provided with the generator).
Check
to
an
external
diagram provided with the generator).
Bring the generator to nominal speed
and measure the voltage output from the
auxiliary winding.
If this is less than 5V, increase the
residual magnetism of the generator
following the instructions in the generator
Use and Maintenance Manual.
Bring the generator to nominal speed
and measure the voltage between P1
and P2.
If this is less than 5V, increase the
residual magnetism of the generator
following the instructions in the generator
Use and Maintenance Manual.
Bring the generator to nominal speed
and measure the voltage PMG output
voltage. If it is less than 100V, contact
Marelli
instructions.
Replace the fuse.
Replace the regulator.
Replace the regulator.
connections
(ref.
connection
connections
(ref.
connection
connections
(ref.
connection
Motori
Service
for
further
32