INSTALLATION
Mobile Home Installation
The England's Stove Works, Inc. outside air kit MUST be used for installation of this unit in a
mobile home. Please see the "Outside Air" section on page 15 for more information regarding
outside air connections.
The outside air inlet must be kept clear of leaves, ice and other debris. Keeping the outside air
inlet free of restriction is crucial to preventing air starvation and smoke spillage.
The pellet stove MUST be secured to the floor of the mobile home using lag bolts and the holes
provided in the bottom of the base for this purpose. Outdoor‐aired space heaters must be
attached to the structure.
The pellet stove MUST be grounded with #8 solid copper grounding wire (or equivalent),
terminated at each end with an NEC approved grounded device.
Carefully follow all clearances listed in the appropriate section of this manual AND follow the
venting manufacturer's minimum clearance requirements. Similarly, be certain the venting
system used is approved for mobile home use.
Installation must be in accordance with Manufacturers Home & Safety Standard (HUD) CFR 3280,
Part 24 as well as any applicable local codes.
Use silicone to create an effective vapor barrier at the location where the chimney or outside air
ducting passes through to the exterior of the structure.
Chimney Cap/Spark Arrestor
Joist Shield/Firestop
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL AND CEILING/ROOF MUST BE
MAINTAINED. DO NOT CUT THROUGH FLOOR JOISTS, WALL STUDS, CEILING TRUSSES OR ANY OTHER
SUPPORTING MATERIAL WHICH COULD BE DETRIMENTAL TO THE STRUCTURAL INTEGRITY OF THE HOME.
IMPORTANT! READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING THE UNIT AS SPECIFIED, AND
ENGLAND'S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT, OR DUE TO UNSAFE INSTALLATION OR
WARNING: DO NOT INSTALL IN A SLEEPING ROOM.
REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED.
USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY QUESTIONS.
CAUTION
13
For high altitude installations
(above 4,000 ft.), the vent pipe
should be increased from 3‐inch
(3") to four‐inch (4").
Roof Flashing and Storm
Collar
Mobile Home Approved
Type L or Type PL Pellet
Vent Pipe