Anomalous Measuring Applications - HT EARTH 2P Manuel D'utilisation

Mesure de la résistance de terre
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.5.1. Anomalous measuring applications

1.
When starting a measurement the
instrument checks the continuity of
measuring cables. If the volt circuit
(red cable S and green cable ES) is
interrupted or its resistance value is
too high, the instrument displays a
screen similar to the one beside. Check
that terminals are properly connected
and that the earth rod is connected to
terminal S and not driven into a pebbly or scarcely conductive ground. In this latter
case pour water around the rod to decrease its resistance value (§ 11.2).
RP>top is displayed when:
 The S rod's resistance R
 The resistance of rod S exceeds the value 1200 + 100 R
earth resistance value)
2.
When starting a measurement the
instrument checks the continuity of
measuring cables.
circuit (blue cable H and black cable
E) is interrupted or its resistance
value
is too high, the instrument
displays a screen similar to the one
beside.
Check
properly connected and that the earth
rod is connected to
terminal H and not driven into a pebbly or scarcely conductive ground. In this latter
case pour water around the rod to decrease its resistance value (§ 11.2).
RC>top is displayed when:
 The H rod's resistance R
 The resistance of rod H exceeds the value 1200 + 100 R
earth resistance value)
3.
When starting a measurement the
instrument checks the continuity of
measuring cables. If the volt circuit
(red cable S and green cable ES) and
the ampere circuit (blue cable H and
black cable E) are both interrupted or
their resistance values are too high,
the instrument displays a screen similar
to the one beside. Check that the
terminals are properly connected and that the earth rods connected to terminals S
and H are not driven into a pebbly or scarcely conductive ground. In this latter case
pour water around the rods to decrease their resistance value (§ 11.2).
RP, RC>top is displayed when:
 The S rod's resistance R
rod's resistance H R
 Both the S rod's resistance and the H rod's resistance exceed the value 1200 +
100 R
X
S
If the ampere
that
terminals
H
S
> 50KΩ is summed up to the ampere circuit
H
[Ω] (where R
is the earth resistance value)
X
> 50KΩ is summed up to the volt circuit
are
> 50KΩ is summed up to the ampere circuit
> 50KΩ is summed up to the volt circuit and the H
EN - 15
GEO416 - GEO416GS
Volt circuit's resistance too
high
Value of input interfering
voltage
Example for 3W mode
[Ω] (where R
is the
X
X
Ampere circuit's resistance
too high
Value of input interfering
voltage
Example for 3W mode
[Ω] (where R
is the
X
X
Both
volt
and
ampere
circuits' resistance too high
Value of input interfering
voltage
Example for 3W mode