11. While the instrument is measuring a
screen similar to the one beside
appears where the instrument's input
interfering
voltage
distance set between auxiliary rods are
displayed. When the message
is displayed do not disconnect or touch
the test leads
When starting measurement the input interfering voltage is measured at both
the volt and ampere circuit. Should it range between 3 V and 9 V, the
instrument carries out measurement and displays the symbol
uncertainty decline of the measurement (§ 9.1
12. When the test is over, should the
ground resistivity value be lower than
the full scale, the instrument emits a
double tone indicating the positive
outcome of the test and displays the
resistivity measurement as well as the
interfering voltage value at the time of
measuring
The resistivity measurement is effected with 4-wire volt ampere method without
being affected by the resistance value of the cables. It is therefore not
necessary to effect compensation of cable resistance or of any extension.
13. When the test is over, should the
ground resistivity value be higher than
the full scale, the instrument emits a
long
tone
indicating
outcome of the test and displays the
screen beside
The full scale is calculated as ρ
for the distance among the rods and R the maximum resistance value which
can be measured by the instrument. The full scale of ground resistivity
measurement depends on the setting of the distance among the rods
The measurements can be stored pressing the SAVE key twice (§ 5.1)
14.
value
and
the
CAUTION
CAUTION
the
negative
CAUTION
MAX
EN - 14
= 2 DIST R where DIST is the value set
GEO416 - GEO416GS
Value of input interfering
voltage and rods' distance
set
indicating the
Measurement
of
ground
resistivity
Value of input interfering
voltage and rods' distance
set
Measurement
of
ground
resistivity higher than the
full scale
Value of input interfering
voltage and rods' distance
set