Electrical Connections
a separate circuit, which must be protected by a
ground Fault Circuit Interrupter (gFCI), is required.
Install a duplex outlet to the studwall underneath the
bathtub, at least 4 inches (102 mm) above the floor.
The duplex outlet is not provided. Because these units
are manufactured with a safe, convenient Magictouch
Whirlpool oN/oFF switch on the bath itself, no remote
switch or timer is necessary. If an optional timer is de-
sired, one is available from Jacuzzi Whirlpool Bath for
120 vaC operation.
DANGER: RISK OF ELECTRIC SHOCK. Connect
only to a circuit protected by a Ground Fault Circuit
Interrupter GFCI.
CAUTION: Operating the motor/pump without
enough water in the bath can cause leaking and
permanent damage to the pump. Before power is
applied to the installation, make sure the switch is
in the OFF position to avoid pump damage.
ELECTRICAL CONNECTION
(FOR SIDE/END DRAIN BATHS)
ELECTRICAL CONNECTION
(FOR MOTOR PUMP ON DRAIN SIDE)
3 PRONG
PLUG
DUPLEX
RECEPT.*
4" MIN.
OR IN
ACCORDANCE
WITH LOCAL
BUILDING OR
ELECTRICAL
CODES
FLOOR
*(NOT PROVIDED)
Copyright © 2007 by Jacuzzi Whirlpool Bath
INSTALLATION
3 PRONG
PLUG
DUPLEX
RECEPT.*
4" MIN.
OR IN
ACCORDANCE
WITH LOCAL
BUILDING OR
FLOOR
ELECTRICAL
CODES
*(NOT PROVIDED)
Electrical Connection 6060 With Heater
On the 6060 with integral skirt, one junction box has
been provided for the pump/motor. the motor is bonded
to the junction box at the factory. To access, remove
skirt access panel. See top view for location.
a separate 120 vaC, 15 aMP dedicated circuit with
gFCI protected outlet (not provided) is required for
®
heater and is to be installed in a junction box. The
junction box is to be hard wired. Follow the bonding
instructions below. With a #8 solid copper wire, bond
the heater to the house electrical panel or approved local
bond. a bonding lug is provided on the heater.
at initial start-up and before each use thereafter with
power oN, push the gFCI test button. the reset button
should pop out. Push this button in to reset. If the inter-
rupter fails to operate in this manner, there is a ground
current flowing or a device malfunction, indicating the
possibility of electrical shock. Turn off power and do
not use the bath until the source of the problem has
been identified and corrected.
60x60 WITH INTEGRAL SKIRT
MOTOR JUNCTION BOX
BONDING TO PUMP/MOTOR
GFCI
CUSTOMER
PROVIDED J-BOX
60x60 WITH INTEGRAL SKIRT
RAPIDHEAT JUNCTION BOX
CUSTOMER
BONDING TO RAPIDHEAT
PROVIDED
GFCI
CUSTOMER
POWER CORD
TO RAPIDHEAT
PROVIDED J-BOX
1
POWER CORD
TO MOTOR
HEATER ON
OVER HEAT
PROTECTION
PUSH TO RESET
U961000K 06/07