4. Setting of the operating parameters
a. Press push-button "P" and apply power to the device.
b. The display shows the message:
c. When the push-button is released, the title of the menu
and the current values of its parameters are displayed in
one-second periods. Press the " " key to interrupt the
scrolling and display only the current parameters.
d. Press the "/" key to jump to the following value of the
parameter currently being set.
e. Press the "P" key to accept the value of the parameter
currently being and switch over to the following menu
item.
f. The last parameter of the setting menu, "EndPro" allows,
selecting "YES", to leave the programming menu and to
take over (to save) the new values. If "NO" is selected,
the programming routine starts again from the begin-
ning, keeping the last input values. They can then be
checked and modified again.
g. For the setting of the numerical values, like for instance
the scale factor, see also 6. Setting of the preset.

5. Programming mode

The first parameter of the menu is the selection of the ope-
rating mode.
Mode pulse counter. See 5.1.
Mode time counter. See 5.2.
Mode frequency meter. See 5.3.
5.1 Pulse counter mode setting
5.1.1 Sub-operating mode
Adding
Output active at count value ≥ preset
Resetting to zero
Subtracting
Output active at count value
Resetting to preset
Adding
Output active at count value = preset
Automatic reset to zero at count value
= preset
Resetting to zero
Subtracting
Output active at count value = 0
Automatic positioning to preset
Resetting to preset
Zumutbare Änderungen aufgrund technischer Verbesserungen vorbehalten.
Pepperl+Fuchs GmbH 68301 Mannheim Telefon (0621)776-11 11 Telefax (0621)776-27-11 11 Internet http://www.pepperl-fuchs.com
5.1.2 Polarity of the inputs
5.1.3 Activation of the 30 Hz filter
5.1.4 Input modes
5.1.5 Setting of the scale factor
0
5.1.6 Decimal point setting
npn: switching to 0 V
pnp: switching to +24 V
max. counting frequency: 20 kHz
max. counting frequency: 30 Hz
Counting and counting direction in-
puts
INP A: counting input
INP B: counting direction input
Differential counting input
INP A: adding counting input
INP B: subtracting counting input
Phase discriminator
INP A: 0° counting input
INP B: 90° counting input
Phase discriminator with multiplica-
tion of the pulses by two
INP A: 0° counting input
INP B: 90° counting input
Each INP A pulse edge is consid-
ered
Scale factor setting range from
00.0001 to 99.9999. Fixed decimal
point set to 4 decimal places.
A "0" setting is not accepted.
The decimal point determines the
number of decimal places dis-
played. It is only used for displaying
purposes and has no influence on
the counting.
0
no decimal place
0.0
one decimal place
0.00
two decimal places
0.000
three decimal places