Operating instructions
Electronic preset counter
1. Description
• 6-digit adding/subtracting counter with one preset
• Very bright 8mm high LED display
• Counting and preset range from –199999 to 999999.
Overshoots and undershoots up to one decade without
loss of pulses. In this case, the display blinks at a 1 Hz
frequency.
• Indication of the active output and display of the preset by
means of LED's
• Programmable as a pulse counter, a frequency meter
/speed indicator or a time counter/operating time counter
• Relay or optocoupler output
• Programming of the functions and of the operating para-
meters by means of the push buttons. Operator guidance
by the display while programming
• Can be programmed:
Operating mode (output signal at 0 or at the preset value,
with or without automatic repetition)
Reset by means of push-button or Reset input
Polarity of the inputs (npn or pnp)
Input mode and scale factor
Decimal point
Output signal in the shape of a positive or negative, timed
or continuous signal
Frequency meter/speed indicator display in 1/s or 1/min
Time counter/operating time counter resolution in s, min,
h or h:min:s, 1, 0.1, 0.01 or 0.001
Start and stop with the time counter/operating time counter
• Supply voltage
90..250 VAC
10..30 VDC
• Optional serial interface
RS232 or
RS422 or
RS485
1.1 Preface
Please read this instruction manual carefully before installa-
tion and start-up. Please observe all warnings
and advices, both for your own safety and for ge-
neral plant safety. If the device is not used in ac-
cordance with this instruction manual, then the
intended protection can be impaired.
1.2 Safety Instructions and Warnings
Please use the device only if its technical condition is per-
fect. It should be used only for its intended pur-
pose. Please bear in mind safety aspects and
potential dangers and adhere to the operating in-
structions and to this addendum at all times. The
safety standards in force for electrical installati-
ons are also to be adhered to.
Zumutbare Änderungen aufgrund technischer Verbesserungen vorbehalten.
Pepperl+Fuchs GmbH 68301 Mannheim Telefon (0621)776-11 11 Telefax (0621)776-27-11 11 Internet http://www.pepperl-fuchs.com
1.3 Use according to the intended purpose
The application area for this device lies in industrial proces-
ses and controls, in the fields of manufacturing lines for the
metal, wood, plastics, paper, glass, textile and other like in-
dustries with a degree of contamination of 2. Over voltages
at the terminals of the device must be kept within the limits
of Over voltage Category II. The device is not suitable for
use in hazardous areas and for areas excluded from EN
61010 Part 1. The device may only be operated indoors as
a panel-mounted device. However, in certain conditions, an
outdoor operation is also allowed. It may be operated up to
an altitude of 2,000 m. Use for any purpose over and bey-
ond this will be deemed as not in accordance with its inten-
ded purpose.
If the device is used to monitor machines or processes in
which, in the event of a failure of the device or an error
made by the operator, there might be the risk of damaging
the machine or causing an accident to the operators, then it
is your responsibility to take the appropriate safety measu-
res.
1.4 Mounting in a control panel
Mount the device away from heat sources and avoid direct
contact with corrosive liquids, hot steam or similar. When
mounting the device, make sure it is sufficiently cooled.
1.5 Mounting instructions
– Remove the mounting clip from the device.
– Insert the device from the front into the panel cut-out, en-
suring the front-panel gasket is correctly seated.
– Slide the fixing clip from the rear onto the housing, until
the spring clamps are under tension and the upper and
lower latching lugs have snapped into place.
1.6 Electrical Installation
This device is powered by the mains voltage! It
must be disconnected from the power supply, be-
fore any installation or maintenance work is car-
ried out. AC-powered devices must only be
connected to the low-voltage network via a switch or circuit
breaker.
Installation or maintenance work must only be carried out
by qualified personnel.
– Correct operation of the device requires the mandatory
use of the appropriate external safety fuse. Advice con-
cerning the recommended fuse protection can be found in
the relevant instruction manual.
In order to respect the fire protection regulations, 8 A/150
VA shall not be exceeded on the counter in case of a de-
fect!
– Do not wire the terminals of the device that are not used.
– The pin assignment of the connectors, as well as the ma-
ximum admissible values, must obligatorily be observed.
– During installation, make sure that the supply voltage and
the wiring of the output contacts (if any) are powered by
the same mains phase, in order not to exceed the max.
voltage of 250 V! The indications of the Instructions ma-
nual must obligatorily be adhered to!
– If the device is equipped with a PE connection, the latter
must obligatorily be connected with a low impedance.
– An EMC-compliant installation is a prerequisite to reach
EC conformity.
Copyright Pepperl+Fuchs, Printed in Germany