Operating Limits With The Heat Recovery Accessory - RHOSS WinPACK HE-A SE TCAEY B-S 2110 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

OPERATING LIMITS WITH THE HEAT RECOVERY ACCESSORY

of the unit without accessory.
mer operating limit is as follows when the recovery is activated:
tue (°C)
Evaporator chilled outlet water temperature.
tuc (°C)
Hot water temperature leaving the recovery unit
RC100:
• The minimum water inlet tuc temperature (°C) allowed is 20°C
• tuc MAX 54°C B-S versions
• tuc MAC 56°C T-Q versions
DS:
• Temperature of hot water produced is 50 to 70°C with a water temperature differential allowed 5 to 10 K
• The minimum water inlet tuc temperature (°C) allowed is 40°C
Note: If the inlet temperature to the recovery unit is lower than the permitted values, it is recommended to use a three-way modulating valve to guar-
antee the minimum water temperature required.
For tue(°C), < 5°C (accessorio BT) it is COMPULSORY to specify the unit's operating temperature when placing the order (evaporator glycol water
inlet/outlet) in order to allow for its correct parametrisation. Condensing control FI10 or FI15, where not already carried out as standard, is also com-
pulsory. Use antifreeze solutions: refer to "
Section I :: User
tuc (°C)
tuc MAX
43
24
5
-8
-4
2
10
15
18
tue (°C)
61
EN
-

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Winpack he-a se tcaey b-s 2120Winpack he-a se tcaey b-s 2140Winpack he-a se tcaey b-s 2150Winpack he-a se tcaey b-s 2170Winpack he-a se tcaey b-s 2200Winpack he-a se tcaey b-s 2220 ... Afficher tout

Table des Matières