2. TECHNICAL DATA
MODEL
TYPE
THERMAL POWER
OUTPUT
OPERATION
FUEL
ELECTRICAL SUPPLY
MOTOR *
IGNITION TRANSFORMER
ABSORBED ELECTRICAL POWER
ELECTRICAL PROTECTION
ELECTROMAGNETIC COMPATIBILITY
* Only with star-delta starter for P 450 T/G burner model
2.1 DIMENSIONS
Boiler front-plate
drilling
mm
A
P 140 T/G
765
P 200 T/G
795
P 300 T/G
858
P 450 T/G
950
* It is possible with a spacer upon request
B
C
365
890
253*-363-473
396
890
281*-391-501
447
1000
314*-444-574
508
1070
346*-476-606
P 140 T/G
P 200 T/G
476 M1
380÷1660 kW
557÷2370 kW
32÷140 kg/h
47÷200 kg/h
1 stage - 2 stage - 3 stage
Light oil, max. viscosity at 20 °C: 6 mm
3N ~ 50 Hz 400 / 230 V
3 ~ 50 Hz 230 V
13,5 A / 230 V
16,4 A / 230 V
8 A / 400 V
9,5 A / 400 V
Prim.: 2 A - Sec.: 2 x 6,5 kV - 35 mA
4,5 kW
IP 40 in accordance with EN 60529 (IEC 529 - 1989)
According to Directive 89/336/CEE (Radiointerference)
Burner
D
E
222
467
250
467
295
496
336
525
41
P 300 T/G
477 M1
478 M1
710÷3560 kW
60÷300 kg/h
2
/s (1,5 °E)
30 A / 230 V
17,5 A / 400 V
5,5 kW
10 kW
F
G
H
230
260
-
260
-
260
-
310
P 450 T/G
479 M1
890÷5340 kW
75÷450 kg/h
45 A / 230 V
26 A / 400 V
15 kW
I
L
225
M14
255
M16
300
M18
350
M20