Commissioning; Before Switching On - Lenze starttec type1 Instructions De Montage

Démarreur moteur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

−25−
(
Stop!
Short circuits or earth faults in the wiring destroy the starttec. Check the
wiring for short circuit and earth fault.
To avoid personal injuries or property damages, check
l
the wiring for completeness, short circuit and earth fault.
l
the "EMERGENCY OFF" function of the complete system.
l
whether the rated motor current is correctly set.
)
Note!
Testing mode without motor
If no motor is connected to the starttec and the starttec is enabled
(X3/28 = HIGH), the mains phase failure detection and the I
respond due to the nature of the system.
To prevent the drive from being switched off with an error message, adjust
the mains phase failure detection and the I
during the testing mode (C0122 = 1, C0123 = 1).
L
EDK71MMXXX−010 DE/EN/FR 5.0

Commissioning

Before switching on

2
xt monitoring
2
xt monitoring to "warning"
7
97

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E71mm402 x a 2a 22 série

Table des Matières