Terminal
Function (bold = Lenze setting)
X3/59
Supply voltage connection +24 VDC
Reference: X3/7
X3/20
DC voltage output + 24 VDC
Reference: X3/7
X3/7
Reference potential
Digital inputs
X3/28
Release/inhibit starttec
X3/E1
Start motor 1
X3/E2
Function not active
Start motor 2
X3/E3
Brake control
Not assigned
X3/E4
X3/E5
Digital outputs
X3/A1
Status of motor 1
X3/A2
Function not active
(Status motor 2)
X3/A3
Status of brake
X3/A4
Not assigned
Motor temperature monitoring
Motor temperature monitoring connection with thermal
X3/T1
contact (NC contact) or PTC
X3/T2
AS interface
AS interface connection
X3/A+
X3/A−
L
Electrical installation
HIGH
starttec released
LOW
starttec inhibited
HIGH
Start motor 1
LOW
Stop motor 1
HIGH
Release brake
LOW
Apply brake
HIGH
Motor 1 is running
LOW
Motor 1 is stopped
HIGH
Brake is released
LOW
Brake is applied
EDK71MMXXX−010 DE/EN/FR 5.0
Connection diagram
Data
+18 VDC − 0 % ... +30 VDC + 0 %)
Min. 200 mA
Max. 1.5 A (all inputs and outputs
are connected)
+18 VDC ... +30 VDC
Max. 500 mA
LOW (0 V ... +3 V)
HIGH (+12 V ... +30 V)
R
= > 4 kW
i
Function in C0410 is freely
assignable
LOW (0 V ... +3 V)
HIGH (+12 V ... +30 V)
Max. 200 mA per output
Function in C0415 is freely
assignable
l
Remove bridge between X3/T1
and X3/T2
Route supply cable to X3/T1
l
and X3/T2 separately
Only active for E71MM402FxAxxx
^ 91
5