Commissioning

Possible settings via DIP switch

ON
1
2
3
The DIP switches on the front serve to set the
ƒ node address (switches 1 ... 6)
ƒ baud rate (switches 7 ... 9)
Switch 10 does not have any function.
The Lenze setting of all DIP switches is OFF.
)
Note!
Settings via codes
In the Lenze setting (all switches OFF), all values from codes C0350 (node
ƒ
address) and C0351 (baud rate) are accepted.
Changes to codes are accepted by:
ƒ
– A voltage supply switch−off and switch−on or
– A "Reset node" with C0358 = 1
C0350 is inactive if at least one of the switches 1 ... 6 has been set to the
ƒ
ON position before the mains is reconnected.
C0351 is inactive if at least one of the switches 7 ... 9 has been set to the
ƒ
ON position before the mains is reconnected.
Detailed information on the codes is provided in the CAN communication
ƒ
manual and the documentation of the standard device.