Finish Framing - After Appliance Installation - Napoleon Vector Serie Manuel D'installation

Masquer les pouces Voir aussi pour Vector Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

single-sided recessed
Ceiling
minimum framing
Ref
LV38-1
K
39 15/16" (101.4cm)
E
20 1/8" (51.1cm)
F
53 13/16" (136.7cm)
J
Optional - Appliance does not need to be elevated above floor
L
73" (185.4cm)
M*
3" (76mm)
*Can only be increased to 4" max by building a protrusion.

finish framing - after appliance installation

L
M*
J
LV50-2
LV62
39 15/16" (101.4cm)
39 15/16" (101.4cm)
20 1/8" (51.1cm)
20 1/8" (51.1cm)
65 13/16" (167.2cm)
77 13/16" (197.6cm)
73" (185.4cm)
91" (231.1cm)
3" (76mm)
3" (76mm)
note:
Shaded components (finish framing) must be
non-combustible materials
Finish framing must be built after the appliance has
been placed in its final position and venting
connected.
This configuration also requires recess
area to use non-combustible facing due
to close proximity to vent.
K
F
E
LV74
39 15/16" (101.4cm)
20 1/8" (51.1cm)
89 13/16" (228.1cm)
91" (231.1cm)
3" (76mm)
Drywall
Insulation
note:
Although the minimum enclosure
height for the LV series is 73",
some venting configurations
that require more vertical rise
will require a larger enclosure to
provide minimum vertical clear-
ance between vent pipes and
combustibles.
W415-1709 / A / 07.27.17
EN
43