rough framing - before appliance installation
EN
4.1.1 minimum clearance to combustible enclosures
single-sided
1" [25mm] minimum
all sides for vertical
venting.
When passing through
a ceiling, use firestop
spacer W500-0028
(not supplied)
0" to side standoffs
1/2" finishing flange
0" to bottom of the
appliance
minimum clearance
Ref
L
note:
The LV series requires a minimum inside enclosure height of 74" measured from the bottom of the appliance.
For temperature requirements, this area must be left unobstructed. It is also recommended that the enclosure
be ventilated at the top and bottom to circulate the hot air.
Although the minimum enclosure height for the LV series is 73", some venting configurations that require more
vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and com-
bustibles.
24
W415-1709 / A / 07.27.17
L
LV38-1
LV50-2
73" (185.4cm)
73" (185.4cm)
note:
Shaded components (finish framing) must be
non-combustible materials
6" [152mm] minimum
0" to back standoffs
LV62
LV74
91" (231.1cm)
91" (231.1cm)
3" [76mm] top
2" [51mm] sides /
bottom
0" to non-combustible
finishing such as brick
and stone
When passing through
a wall, use firestop
spacer W615-0162
(supplied with W010-
4178 firestop spacer
assembly)