6 - SPECIAL FUNCTIONS SETTINGS
6.3) TEMPERATURE DIFFERENTIAL (ON/OFF)
The chronothermostat is set (in factory) to work
preset differential value of
0.3°C
The differential value must be set according to the system's thermal inertia.
A low value is recommended for systems with radiators (e.g. cast iron) and a
high value for systems with fan coils.
This function can be protected by a password (see chapter ).
The differential value may be displayed and changed as follows:
Keep
t1
pressed until the existing differential value blinks on the display
(example in fig. 36 - factory setting
Modify the value (from 0.2 to 0.7) using the keys
Press
OK twice
the desired value is obtained to return to program operation
(example in fig. 37).
Very low differential on/off values (for example 0.2°C) may
result in increased frequency of control transmission to the
receiver, resulting in more rapid battery depletion with
respect to data stated.
78
Differential mode ON/OFF
.
0.3C
).
(example in fig. 36).
Example:
°C
with a
20°
19,7°
Device in operation
8
- set "SET": 20°C in WINTER mode
- Set differential 0.3
ex. h
On
Off
On
Device in operation
press for 4 seconds
.
t1
t2
t3
0
2
4
6
8
10 12 14 16 18
20 22
.
t1
t2
t3
0
2
4
6
8
10 12 14 16 18
20 22
press 2 times
ysteresis
: 0,3
Time
fig. 36