COOLIG TOWER APPLICATIOS
(WATER-COOLED MODELS)
A water cooling tower installation does not
require modification of the ice machine.
The water regulator valve for the condenser
continues to control the refrigeration
discharge pressure.
It is necessary to know the amount of heat
rejection and the pressure drop through
the condenser and water valves (inlet and
outlet) when using a cooling tower on an
ice machine.
• Water entering the condenser must not
exceed 90°F (32°C).
• Water flow through the condenser
must not exceed 5 gallons (19 liters) per
minute.
• Allow for a pressure drop of 7 psi (50
kPa) between the condenser water inlet
and the outlet of the ice machine.
• Water exiting the condenser must not
exceed 110°F (43°C).
18
Remote Condenser/Line Set
Installation
Remote
Ice Machine
Single Circuit
Condenser
K1000
JCT1200
K1700
JCT1500
*Line Set
Discharge
RT
(1.27 cm)
RL
(1.27 cm)
Air Temperature Around the Condenser
Minimum
-20°F (-29°C)

otice
Remote systems are only approved and
warranted as a complete new package.
Warranty on the refrigeration system will
be void if a new ice machine head section
is connected to pre-existing (used) tubing
or remote condensers.
Part Number: 000014142 Rev 02 5/17
Section 2
Line Set*
RT-20R-R410A
RT-35R-R410A
RT-50R-R410A
RL-20R-R410A
RL-35R-R410A
RL-50R-R410A
Liquid Line
Line
1/2"
5/16"
(.79 cm)
1/2"
3/8"
(.95 cm)
Maximum
120°F (49°C)