SMA Solar Technology AG
5.2.5 Sunny Mini Central 9000TL/10000TL/11000TL
avec Reactive Power Control
Nom
ACVtgRPro*
AID-Esk-Alpha*
DC-Offset_Max*
DGS-HystVolNom*
DGS-PWMVolNom*
E_Total
Fac-delta‒*
Fac-delta+*
Fac-Limit delta
Fac-Start delta
Fan-Test
h_Total
LDVtgC*
Mode de service
P-HzStop*
P-HzStr*
P-W*
P-WCtlHzMod*
P-WGra*
P-WMod*
PF-PFExt*
PF-PF*
Pmax (SMC 9000TLRP-10)
Pmax (SMC 10000TLRP-10)
Pmax (SMC 11000TLRP-10)
Description technique
Valeur/plage
230 V ... 300 V
0 grd/% ... 40 grd/%
100 mA ... 5 000 mA
0 % ... 60 %
40 % ... 100 %
0 kWh ... 200 000 kWh
0,1 ... 6 Hz
0,1 ... 5 Hz
0 Hz ... 5 Hz
0 Hz ... 5 Hz
0 ... 1
0 h ... 200 000 h
0 V ... 50 V
Service Mpp
Tension const.
Arrêt
0 Hz ... 5 Hz
0 Hz ... 5 Hz
0 W ... 11 110 W
Off
On
10 %/Hz ... 100 %/Hz
Off
WCnst
WCtlCom
Overexcited (surexcité)
Underexcited (sous-excité)
0,8 ... 1,0
0 W ... 9 090 W
0 W ... 10 100 W
0 W ... 11 110 W
Plages de valeur et réglages usine
Valeur par défaut
253 V
en fonction de la norme du pays
en fonction de la norme du pays
5 %
70 %
0 kWh
en fonction de la norme du pays
en fonction de la norme du pays
2 Hz
1 Hz
0
0 h
en fonction de la norme du pays
Service Mpp
0,05 Hz
0,20 Hz
11 000 W
Off
40 %/Hz
WCtlCom
Underexcited
1
9 000 W
10 000 W
11 000 W
SB_SMC_WB_Par-TFR104250