Setting
Cooling thermoregulation
To set the temperature adjustment
parameters, simultaneously press and
hold back "
" and "OK" buttons until
"Enter code" appears on the display.
Turn the knob to enter the technical
code (234) then press OK; the display
will show Technical area.
Turn the knob and select
-
Complete Menu.
Press the OK button..
4
Zone 1 Parameters
Press the OK button.
Turn the knob and select:
4.5
Cooling
Press the OK button.
Turn the knob and select:
4.5.0 T set cool Z1
Press the OK button. Turn the knob and
set the delivery temperature setpoint,
for thermoregulation off or fi xed point.
Press the OK button. Turn the knob and
select:
4.5.1
Zone 1 Cooling Temp Range
Press the OK button.
Turn the knob and select the tempera-
ture range:
- Fan Coil
- Underfl oor
Press the OK button.
Turn the knob and select:
4.5.2
Thermoregulation
Press the OK button. Turn the knob and
set the type of temperature adjustment
installed:
Graph A (Fan Coil)
°C
12
11
10
9
8
7
6
0
5
10
15
see parameter 4.5.3
86 / GB
- 0 ON/OFF
- 1 Fix Flow T
- 2 Outdoor T Only
4.5.3
Slope
Press the OK button. Turn the knob and
set the curve in relation to the type of
cooling system, then press the OK but-
ton.
- Fan Coil (curves from 18 to 33)
- Underfl oor (curves from 0 to 30)
The checking process for the suitability
of the curve requires a long period of
time during which several adjustments
may be necessary.
When the outdoor temperature rises
(summer), three conditions may arise:
1. The temperature of the room may
rise, indicating that a gentler curve
should be set;
2. The temperature of the room may
fall, indicating that a steeper curve
should be set;
3. The temperature of the room re-
mains constant, indicating that the
set curve is exactly right.
Once you have found the curve which
maintains the room temperature at a
constant level, check the actual tempe-
rature value.
IMPORTANT:
If the room temperature is higher than
the desired value, the curve must be
shifted downwards decreasing the pa-
33
25
18
20
25
30
35
40
outdoor temperature
Graph B (Underfl oor)
°C
23
30
25
22
20
20
15
21
10
19
5
18
17
45 °C
0
5
see parameter 4.5.3
meters 4.5.3. If the room temperature
is too low, the curve should be shifted
upwards increasing the pameters 4.5.3.
If the temperature of the room corre-
sponds to the desired value, the curve
is correct.
In the graph below, the curves have
been divided into two groups:
- fan coil systems (graph A)
- under-fl oor systems (graph B)
Press the OK button. Turn the knob and
select:
4.5.4
Off set
Press the OK button. Turn the knob and
set the most suitable value. Press the OK
button to confi rm.
Turn the knob and select:
4.5.6
Max T
Press the OK button. Turn the knob and
set the most suitable value according to
zone temperature range (see parameter
4.5.1), then press the OK button.
Turn the knob and select:
4.5.7
Min T
Press the OK button. Turn the knob and
set the most suitable value according to
zone temperature range (see parameter
4.5.1), then press the OK button.
Repeat the steps described to set the
values for zones 2 (if present), selecting
menu 5.
10
15
20
25
30
outdoor temperature
45 °C
35
40