4.6 Electrical Specs
1.
Voltage: 230VAC, 60Hz, Single Phase
2. Amps: 10.9
3. Speed Range: 600-3450 rpm
Use copper conductors only. For indoor & outdoor use. Connect pump to a 15 amp branch circuit in accordance with
local codes, regulations, and the National Electric Code (NEC). A disconnecting means located at least 5 ft. from the
inside wall of the pool, spa, or hot tub must be provided.
4.7 Voltage
Voltage at pump MUST NOT be more than 10% above or below nameplate rated voltage, or components may
overheat, causing overload tripping and reduced component life. If voltage is less than 90% (207 VAC) or more than
110% (253 VAC) of rated voltage (230 VAC) when pump is running at full load, consult the power company.
4.8 Grounding and Bonding
1.
Install, ground, bond, and wire pump in accordance with local or national electrical code requirements.
2. Permanently ground pump. Use green ground terminal provided under access plate; use size and type wire
required by code. Connect ground terminal to electrical service ground.
3. Bond pump to pool structure. Bonding will connect all metal parts within and around the pool with a continuous
wire. Bonding reduces the risk of a current passing between bonded metal objects, which could potentially
cause electrical shock if grounded or shorted. Reference NEC codes for all wiring standards including, but not
limited to, grounding, bonding and general wiring procedures.
4. Use a solid copper conductor, size 8 or larger. Run wire from external bonding lug to reinforcing rod or mesh.
Connect a No. 8 AWG (8.4 mm
wire connector provided on the motor housing and to all metal parts of swimming pool, spa, or hot tub, and to
all electrical equipment, metal piping (except gas piping), and conduit within 5 ft. (1.5 m) of inside walls of
swimming pool, spa, or hot tub.
4.9 Wiring
WARNING
(NEC).
1.
Pump MUST be permanently connected to circuit. If other lights or appliances are also on the same circuit, be
sure to add their amp loads before calculating wire and circuit breaker sizes. Use the circuit breaker as the
master On-Off switch.
2. If the HCP3000 SERIES Variable Speed Pump is being used to replace an existing pump that was controlled by a
separate mechanical time clock, the HCP3000 SERIES Variable Speed Pump should be connected directly to the
line power supply, bypassing the time clock. The time clock can then be used to power other equipment (such
as a heater, heat pump, or booster pump) that requires the filter pump to be operating when used. If the time
clock is used in this manner, it should be set to power the equipment during a time cycle when the HCP3000
SERIES Variable Speed Pump is operating at an appropriate flow rate to operate the other equipment, as defined
by the timers set in the Timer Menu. See section 6.7
Page 10 of 76
2
) [No. 6 AWG (13.3 mm
– All electrical wiring MUST conform to local codes, regulations, and the National Electric Code
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HCP3000 SERIES Variable Speed Pump
2
) for Canada] solid copper bonding wire to the pressure
ISHCP3000VSPC Rev -B