3.0 Before Installation
3.1 Safety Requirements
Be sure to preview the standard operating proce-
`
dures (SOP) and ensure local building andelectrical
codes are reviewed before installing the DC Wallbox
charger.
The DC Wallbox charger should be installed by a
`
qualified technician according to the instruction
manual and local safety regulations.
Use appropriate protection when connecting to the
`
main power distribution cable.
Disconnect switch for each ungrounded conductor of
`
AC input shall be provided by others in accordance
with the National Electric Code, ANSI/NFPA 70.
CAUTION TO REDUCE RISK OF FIRE,
FOR 1 PHASE 200VAC-277VAC INPUT,
IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE, ANSI/NFPA 70, THE
UPSTREAM CIRCUIT BREAKER SHOULD BE
INSTALLED WITH A RATED CURRENT OF
175A.
CAUTION TO REDUCE RISK OF FIRE, FOR
3 PHASE 480VAC INPUT, IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE,
ANSI/NFPA 70, THE UPSTREAM CIRCUIT
BREAKER SHOULD BE INSTALLED WITH A
RATED CURRENT OF 40A.
CAUTION TO REDUCE RISK OF FIRE, FOR
3 PHASE 208VAC INPUT, IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE,
ANSI/NFPA 70, THE UPSTREAM CIRCUIT
BREAKER SHOULD BE INSTALLED WITH A
RATED CURRENT OF 100A.
Bosch Automotive Service Solutions Inc.
EV2000 Series Wallbox Charger Installation and Operation Manual| 3 | en
3.2 Accessory Kit
3.3
Recommended Tools
The following tools are recommended for DC Wallbox
Charger installation:
(1x) Voltmeter or digital multi-meter
`
(1x) Water level
`
(1x) Hammer
`
(1x) Concrete drilling machine
`
(1x) Wire cutters / strippers
`
(1x) Torx® Tamper-Resistant T20 screwdriver
`
(1x) No.8 Flathead screwdriver
`
(1x) No.6 Flathead screwdriver
`
(1x) No.2 Philips screw driver
`
(1x) M50 conduit hub, conduit and wrench for main
`
power wires
(1x) M25 conduit hub, conduit and wrench for
`
Ethernet
(2x) Ring terminal RNB70-10 for L/N wire (#2/0
`
AWG, 90°C copper wire) in models with 240V and
277V single-phase input
(3x) Ring terminal RNB38-6 for L1/L2/L3 wire (#2
`
AWG, 90°C copper wire) in models with 208V three-
phase input
(4x) Ring terminal RNB14-6 for L1/L2/L3/N wire (#6
`
AWG, 90°C copper wire) in models with 480V three-
phase input
(1x) Ring terminal RNB14-6 for PE/ground wire (#6
`
AWG, 90°C copper wire)
579604 | REV. C | June 2020