Dimensions drawings actuator and
indicator elements
Dimensions in mm
Puschbutton
Double pushbutton
actuator
Key-operated switch actuator
Key-operated pushbutton actuator
Mushroom-head pushbutton actuator
"EMERGENCY STOP"
Mushroom-head pushbutton actuator
X = fixing dimensions
24
24
24
24
24
Cooper Crouse-Hinds GmbH
Explosion-protecded distributions GHG 619
1.14

Multi-function relay

EC-Type Examination Certificate:
Explosion protection:
Temperature range:
Rated voltage:
Control voltage:
Rated current:
Rated switch capacity:
Back up fuse:
Time ranges (optional):
Control functions:
actuator
Terminal cross section:
Component size:
Weight:
Contacts for functions:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
1.15
Motor starter 4 kW
EC-Type Examination Certificate:
Explosion protection:
Temperature range:
Rated voltage:
Control voltage:
Rated current:
Rated switching capacity Main contacts AC 3:
Rated switching capacity Aux. contacts AC 11:
Terminal cross section:
Switching contacts 1, 2, 3, 4, 5, 6,
Control contacts A1, A2
Aux. contacts optionally 21,22, 23,24, 33 34
Component size:
Weight:
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
1.16

Thermal overcurrent relay

EC-Type Examination Certificate:
Explosion protection:
Temperature range:
Rated voltage:
Control voltage:
Continuous operation current I
Tripping current:
Function:
Terminal cross section:
Switch contacts 1,2,3,4,5,6
Control contacts 95, 96, 97, 98
Component size:
Weight:
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 440V AC
12V - 400V AC
6A
AC 11
230V/3A
DC 11
24V/1A,
6A gL
0.05 - 1sec•.; 0.15 - 3sec.;
3 - 60sec.;
0.15 - 3h;
11
-
12
-
16
-
21
-
22
-
42
-
Main contacts max. 2x 10mm²
Control contacts
max. 2x 2.5mm²
Aux. contacts
max. 2x 2.5mm²
2
ca. 0.94kg
11, 21 and 42
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 690V AC
12V - 690V AC
Main contacts
Aux. contacts
230V/2.2kW
230V / 4A
max. 2x 10mm²
max. 2x 2.5mm²
max. 2x 2.5mm²
3
ca. 1.72kg
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 690V AC
up to 690V AC
:
6A
th
0.16A ........ 16A
thermal release with phase-failure protection
max. 2x 10mm²
max. 2x 2.5mm²
2
ca. 1.10kg
12V - 240V DC
440V/3A
60V/ 0.35A,
220V/0.20A
0.5 - 10sec.;
0.5 - 10min.;
3 - 60min.;
0.5 - 10h;
3 - 60h
delayed pick-up
delayed reset
delayed pick-up and reset
cut-in wiping
cut-off wiping
blinking
/ 3.0 Nm
/ 1.5 Nm
/ 1.5 Nm
12, 16 and 22
12V - 230V DC
up to 20A
up to 6A
400V/4kW
690V/4kW
/ 3.0 Nm
/ 1.5 Nm
/ 1.5 Nm
/ 3.0 Nm
/ 1.5 Nm