Contakt arrangements
Ex 23 / Ex28 / Ex 29 switch
Switch mechanism
4
5
switch mechanism
7
8
Explosion-protecded distributions GHG 619
1.6
Current surge switch
Circuitry
EC-Type Examination Certificate:
Code
Explosion protection:
Temperature range:
Rated voltage:
6011
Rated operating voltage:
Rated current:
Rated switching capacity:
Terminal cross section:
6019
Switching contacts 1, 2, 3, 4
Control contacts A1, A2
Komponent size:
6060
Weight:
Contact arrangement:
6062
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
6065
1.7
20A installation contactor
EC-Type Examination Certificate:
6033
Explosion protection:
Temperature range:
Rated voltage:
6170
Control voltage:
Rated current:
Rated switching capacity:
. 021
Back-up fuse:
Terminal cross section:
Switching contacs 1, 2, 3, 4
Control contacs
. 023
Component size:
Weight:
. 024
Contact arrangement:
The technical data relates to standard built-in apparatus.
. 061
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
. 063
1.8
24A installation contactor
EC-Type Examination Certificate:
. 066
Explosion protection:
Temperature range:
Rated voltage:
Control voltage:
. 067
Rated current:
Rated switching capacity – main contacts:
. 049
AC1 - 3-phase:
AC3 - 3-phase:
DC 3
. 037
DC 3
DC 3
Rated switching capacity – aux. contacts:
. 191
Back-up fuse:
Terminal cross section:
Switching contacts 1, 2, 3, 4, 5, 6,
Control contacts A1, A2
Aux. contacts 7(13), 8(14) /optional ly21,22,33,34 max. 2x 2.5mm²
Component size:
Weight:
Contact arrangement:
6
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
Special
or the data on the type label shall be observed.
9
A1, A2
1 current path
2 current paths
3 current paths
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 400V AC
8V to 400V AC
16A
16A / 250V AC
max. 2x 10mm²
/ 3.0 Nm
max. 2x 2.5mm²
/ 1.5 Nm
0
ca. 0.55kg
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 250V AC
24V to 250V AC
20A
AC 1 230V / 4,0kW
AC 3 230V / 1,3kW
20A gL
max. 2x 10mm²
/ 3.0 Nm
max. 2x 2.5mm²
/ 1.5 Nm
0
ca. 0.55kg
1NO+1NC
2 NO
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 400V AC
24V to 400V AC
Main contacts
up to 24A
Aux. contacts
up to 6A
230V / 9.0kW
230V / 2.2kW
60V / 4A
60V / 14A
60V / 24A
AC 15
230V / 4A
35A gL
max. 2x 10mm²
/ 3.5 Nm
max. 2x 2.5mm²
/ 1.5 Nm
/ 1.5 Nm
3
ca. 1.20kg
Main contacts
4 NO
1NO+1NC
Cooper Crouse-Hinds GmbH
8V to 220V DC
10A / 400V AC
2 NC
400V / 16 kW
400V / 4.0kW
220V / 0.2A
220V / 1.0A
220V / 4.0A
400V / 3A
Aux. contacts
2 NC
21
21
21
21