Contact Arrangements; Bus Bar System; Circuit Breaker - Cooper Crouse-Hinds GHG 619 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 1
Connection diagrams
Connection
up to 35mm²
up to 240mm²
Fig. 2
Bus bar system – horizontal connection
Fig. 3
Bus bar system – vertical connection
Fig. 4
Connection Main-;
Aux.-/Signal contact
A
B
Explosion-protecded distributions GHG 619
1.2
Bus-bar system
EC-Type Examination Certificate:
Explosion protection:
Rated voltage:
Rated current:
Short-circuit current:
Back-up fuse:
Rated short-time current (1s):
Terminal cross section:
Min. terminal cross section:
Rated current:
Overall length of unit:
1.3
Circuit breaker, 1-, 2-, 3-, 4-pole
EC-Type Examination Certificate:
Explosion protection:
Temperature range:
Rated voltage:
Maximumvoltage acc. NEC for
"p" Type
GHG 612 11.. R0013 - 27
GHG 612 21.. R0013 - 27
GHG 612 31.. R0013 - 27
GHG 612 41.. R0013 - 27
Rated current:
Rated switching capacity:
Back-up fuse:
Terminal cross section
Main contact:
with insert ring types:
Aux./Signal contact:
Test torques
Main contacts
Aux. contacts
Component size:
Weight:
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
Tripping characteristic of circuit breaker last page
* Circuit breakers with signal contacts are built into component enclosures in the next size.
PTB 99 ATEX 1044
Ex e II
up to 730V AC
max. 180A
max. 47kA
max 250A gL
1378A
max. 240mm²
1x 120mm²
250A (see Safety Instructions, page 29)
max. 6.80m
up to 240mm²
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
Main contact
Aux. contact
up to 400V AC
up to 240V AC
up to 480V AC
up to 240V AC
Main contakt
Aux./Signal contakt
0.5A up to 40A
up to 5A
6kA
dep. on rated current, up to 100A
1x 2.5 mm² up to 2x 10 mm² (Fig. 4 A or B)
max. 2x 16 mm² (Fig. 4 B)
1x 1.5 mm² up to 2x 2.5 mm² (Fig. 4 A)
3.0 Nm
1.5 Nm
1
2
ca.
0.58kg
0.96kg
1-pole *
2-pole *
Cooper Crouse-Hinds GmbH
up to 35mm²
3
4
1.24kg
1.62kg
3-pole *
3-pol.+N
19
19
19
19
19

Publicité

Table des Matières
loading