40A Installation Contactor - Cooper Crouse-Hinds GHG 619 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Contact arrangements
Ex41 - GHG 411 switches
Switch mechanism
4
5
switch mechanism
7
8
Contact arrangements
Ex41 - GHG 411 Pushbutton
Mushroom-head pushbutton with interlock
2 Ö
2 S
Mushroom-head pushbutton with key release
2 Ö
2 S
Key-operated pushbutton
2 Ö
2 S
Pushbutton
2 Ö
2 S
Double pushbutton
2 Ö
2 S
22
22
22
22
22
Cooper Crouse-Hinds GmbH
Explosion-protecded distributions GHG 619
1.9

40A installation contactor

Circuity
EC-Type Examination Certificate:
Code
Explosion protection:
Temperature range:
Rated voltage:
6060
Control voltage:
Rated current:
Main contacts
Aux. contacts
6062
Rated switching capacity - main contacts:
AC1 - 3-phase:
AC3 - 3-phase:
6065
DC 3
DC 3
DC 3
. 061
Rated switching capacity - aux. contacts:
Back-up fuse:
Terminal cross section:
. 063
Switching contacts 1, 2, 3, 4, 5, 6,
Control contacts A1, A2
Aux. contacts 7(13), 8(14) /optional ly21,22,33,34 max. 2x 2.5mm²
. 067
Component size:
Weight:
Contact arrangement:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
6
Special
9
1S+1Ö
1S+1Ö
1S+1Ö
1S+1Ö
1S+1Ö
PTB 98 ATEX 1087U
Ex de II C
for use in temperature classes T4-T6
up to 400V AC
24V to 400V AC
NO - up to 40A
up to 6A
230V / 15.2kW
230V /
1 current path
60V / 5A
2 current paths
60V / 16A
3 current paths
60V / 34A
AC 15
63A gL
max. 2x 10mm²
max. 2x 2.5mm²
4
ca. 1.65kg
NC - up to 32A
400V / 26kW
5.5kW
400V / 11kW
220V / 0.3A
220V / 1.1A
220V / 4.5A
230V / 4A
400V / 3A
/ 3.0 Nm
/ 1.5 Nm
/ 1.5 Nm
Main contacts
Aux. contacts
4NO
1NO+1NC 2NO