Fronius Galvo
Input Data
Recommended PV power
MPP voltage range
Start voltage
Max. input voltage
at 1000 W/m²/57.2 °F (14 °C) in an open circuit
Nominal input voltage
Nominal input current
Max. input current
Max. short circuit current of the solar modules
Max. continuous utility backfeed current
Max. continuous backfeed current from other MPPT
or battery inputs
Output Data
Nominal output power (P
P
at +122 °F (50 °C)
nom
Max. output power
Nominal mains voltage
Mains voltage tolerance
Operating AC voltage range
Adjustment range for mains voltage
Voltage trip limit accuracy
Voltage clearing time setting range
Nominal output current
Phases
Maximum continuous utility backfeed
3)
current
Synchronization in-rush current
Max. output residual current per dura-
tion
Nominal output frequency
Operating frequency range
Adjustment range for grid frequency
Frequency trip limit accuracy
Frequency clearing time setting range
Total harmonic distortion
50
2)
)
at 208 V
nom
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
3)
at 208 V
at 220 V
at 240 V
2.5-1 208–240
3.1-1 208–240
2.0–3.25 kWp
2.5–4.0 kWp
165–440 V DC
185 V
1)
550 V DC
330 V
8.0 A
10.0 A
16.1 A
20.0 A
24.1 A
30.1 A
3)
0.0 A
4)
0.0 A
2500 W
2930 W
2500 W
3100 W
2500 W
3100 W
2500 W
2600 W
2500 W
2650 W
2500 W
2750 W
2500 W
3100 W
208 V/220 V/240 V
-12%/+10%
183–229 V
194–242 V
211–264 V
104–288 V
104–288 V
104–288 V
1% of nominal value
5)
0.016–21.0 s
12.0 A AC
14.1 A AC
11.4 A AC
14.1 A AC
10.4 A AC
12.9 A AC
2
0 A
36.0 A/9.4 ms
456 A/1.9 ms
440 A/1.5 ms
488 A/1.4 ms
60 Hz
45.0–65.0 Hz
45.0–65.0 Hz
0.05 Hz
5)
0.016–600 s
< 4%