Program 48- Solar power system with 2 consumers

S1
A1
A2
S1
min1
diff1
diff2
A1
S2
S3
max1
max2
Program 48: Pump A1 runs when:
 S1 is greater than the threshold min1  and S1 is greater than S2 by the difference diff1
 and S2 has not exceeded the threshold max1.
Pump A2 runs when:
 S1 is greater than the threshold min1  and S1 is greater than S3 by the difference diff2
 and S3 has not exceeded the threshold max2.
All programs +1:
Instead of the two pumps, one pump and a three-way valve are used (pump-valve system). Speed
control: Observe the comments on page 7!
Without a priority allocation, tank 2 is filled by priority.
A1 ... common pump
All programs +2:
In addition, if S4 exceeds the threshold max3, pump A1 is switched off.
All programs +4: Both solar loops have separate switch-on thresholds at S1:
output A1 retains min1, and A2 switches at min2.
The priorities for TK1 and TK2 can be set in the parameter menu under PA. In addition, a solar
priority function can be set for this diagram in the menu PRIOR.
8
S4 for program +2
SP1
TK1
S4
S4
S2
required settings:
max1 ... limit TK1 S2
max2 ... limit TK2 S3
max3 ... see all programs +2
A2
min1 ... switch-on temp. coll. S1
min2 ... see all programs +4
... coll. S1 – TK1 S2
diff1
... coll. S1 – TK2 S3
diff2
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2
A2 ... Valve (A2/S receives power when filling tank TK2)
SP2
TK2
S3
 A1
 A2
 A1, A2
 A1
 A2