UVR 61-3 Version 9.5 EN-FR Triple-loop universal controller Regulateur universel à trois circuits Operation Installation instructions Mode d'emploi Instructions de montage...
Page 2
The entire instruction manual can be downloaded from: www.ta.co.at section DOWNLOADS Vous pouvez télécharger le mode d’emploi complet de la page Internet: www.ta.co.at domaine DOWNLOADS English SINGLE AND TRIPLE-LOOP UNIVERSAL CONTROLLER.............5 Français REGULATEUR UNIVERSEL À UN-/TROIS CIRCUITS…………………………………………36...
English SINGLE AND TRIPLE-LOOP UNIVERSAL CONTROLLER The UVR61-3 unit has various functions for use in solar power systems and heating systems: thermostat, differential temperature, and speed control. The desired control function is the result of the program number that is input. Overview of functions: ...
Page 4
O AUTO ..........................30 Status display Stat ........................30 The menu Men ..........................32 Brief description .......................... 33 Troubleshooting ........................34 Table of settings ........................35 Français REGULATEUR UNIVERSEL À UN-/TROIS CIRCUITS L’appareil UVR61-3 est équipé de différentes fonctions de thermostat, de différence de température et de réglage de vitesse pour la mise en oeuvre dans les installations solaires et les systèmes de chauffage.
Page 5
Valeurs de réglage (max, min, diff) ..................... 55 Heure ............................57 Date DAT ............................ 57 Masques de temps MAT (3 fois) ....................57 Fonction minuterie TIMER ......................58 Attribution des sorties libres A2/A3 <= OFF ................59 Mode automatique / manuel ....................... 60 S AUTO ..........................
English Safety requirements These instructions are intended exclusively for authorised professionals.All installation and wiring work on the controller must only be carried out in a zero-volts state. The opening, connection and commissioning of the device may only be carried out by competent personnel. In so doing, all local security requirements must be adhered to.
English Hydraulic diagrams The entire instruction manual with all schemes and programs can be downloaded from: www.ta.co.at section DOWNLOADS Pump valve system of the programs 49, 177, 193, 209, 225, 226, 227, 417, 625: Speed control (if activated): Control output COP 1: The speed control only operates when filling cylinder 1. If max1 is exceeded on the sensor 2 (filling cylinder 2 or 3), the pump is operated on the highest speed.
English Program 48 - Solar power system with 2 consumers S4 for program +2 Required settings: min1 max1 … limit CYL 1 S2 A1 max2 … limit CYL 2 S3 A2 diff1 diff2 max3 … see all programs +2 min1 …...
English Program 80 - Single solar power system and cylinder load from boiler Required settings: min1 min2 max1 … limit CYL S2 A1 max2 … limit CYL S4 A2 diff1 diff2 max3 … see all programs +4 min1 … switch-on temp. coll. S1 ...
English Program 320 - Layered cylinder and load pump Only effective with speed control activated. (Absolute value control system: AC N1) Required settings: min1 min3 <min2 >min2 max1 … limit CYL S2 A1 max2 … limit CYL S4 A2 max3 …...
English Program 624 - Solar power system with one consumer and swimming pool S4 for program +2 CYL 1 CYL 2 Required settings: min1 max1 … limit CYL 1 S2 A1 diff1 diff2 max2 … limit CYL 2 S3 ...
English Installation instructions Installing the sensors The sensors must be arranged and installed properly for the system to function correctly. To this end, make sure that they are completely inserted in the immersion sleeves. The threaded cable connections provided can be used to provide strain relief. The clip-on sensors must be insulated to protect them from being influenced by the ambient temperature.
English Hot water sensor: When the control system is used in hot water systems with an external heat exchanger and variable-speed pump, changes in the amount of water have to be reacted to quickly. Hence, the hot water sensor has to be put directly on the heat exchanger’s outlet. A t-shaped connector should be used to insert the ultrafast sensor (special accessory) in the outlet using an o- ring along the NIRO tube (inoxydable).
English Installing the unit CAUTION! ALWAYS PULL THE MAINS PLUG BEFORE OPENING THE CASE! Only work on the control system when it is dead. Unscrew the screw on the top of the case and take off the lid. The control electronics is in the lid. Contact pins are used to restore the connection to the clamps in the lower part of the case when it is put back on.
The bi-directional data link (DL-Bus) was developed for the ESR/UVR series and is only compatible with products of the Technische Alternative company. Any cable with a cross section of 0.75 mm² can be used for the data link (e.g. twin-strand) having a max. length of 30 m. For longer cables, we recommend the use of shielded cable.
English Operation The large majority contains all of the icons needed for all of the important information as well as a plain text field. Navigation with the co-ordination keys has been adapted to the display arrangement ...
English The main level Temperature Temperature Temperature Sensor 1 Sensor 2 Sensor 6 Volume flow Wind velocity External value 1 Only displayed Only displayed Only displayed if if S6 = VSG if S6 = WS external DL is activated External value 9 Legionella function Speed stage Only displayed if...
Page 20
English T1 to T6 Displays the value measured at the sensor (S1 - T1, S2 - T2, etc.). The display (unit) depends on the settings of the sensor type. Display types: Temperature in °C Radiation in W/m Digital status 1 = ON (radiation sensor) (digital input) If in the SENSOR menu (main menu ENTER/Men) one sensor is set to OFF, then the...
English Display of the system’s status. Depending on the program selected, various system Stat: statuses are monitored. If any problems have occurred, this menu contains all of the information. The navigation keys on the parameter level (, ) allow you to select the icons under the Par: temperature display and the text line.
English The parameter menu Par Code to enter menu Version number Program number Linking of output Priority assignment Max limit switch-off (only for programs threshold (3 times) with priority Max limit switch-on Min limit switch-on Min limit switch-off only displayed threshold (3 times) only displayed (3 times)
English Assign free outputs Automatic / manual Automatic / manual (according to mode (3 times) for mode (2 times) for diagram) outputs 1 – 3 the control outputs Brief description Code to enter the menu. The other menu items are only displayed once the correct CODE code has been entered.
English Code to enter menu Version number Program number Code number CODE The other menu items of the parameter menu are only displayed after input of the correct code number (code number 32). Software version VER Display of the software version. It cannot be changed as it indicates the intelligence of the device and must be provided if there are any queries.
English Priority assignment PA Priorities can be set for program diagrams with multiple consumers on one heat generator. This menu item is only displayed for program diagrams with priority. The priority assignment (output assignment) is adapted to the specific program diagram. The priority assignment always refers to the pumps.
Page 26
English Example: Program number 0 Max limit switch-off Max limit switch-on Min limit switch-on value value value Min limit switch-off Difference switch-on Difference switch-off value threshold threshold max When a sensor reaches this temperature, the output is blocked. (ex works = 75°C) max ...
English Time Example: 16:34 = Display of time. The time is set by pressing enter and the navigation keys. Press the key again to switch between minutes and hours. Time The correct setting of date and time can be useful even if the time windows are not NOTICE: used.
English Number of the time window Assigned outputs Release time Block time In the example, output 1 has been assigned to time window 1 (index). This output can be switched between 6:30 AM and 9:30 PM. The following outputs are assigned to the time window. (ex works = --) A(AND) In the time window the respective program determines the status of the selected outputs.
English In the example the timer function is assigned to output 1. The output is released for 5 hours and blocked for 2 hours. The timer function is assigned the following outputs. (ex works = --) OPA A (AND) During the release time the respective program determines the status of the selected outputs.
English WARNING: The switch function does not relate directly to the allocated output, rather only to its function in the program diagram, in which respect a possible priority allocation is not considered.If the output is to be affected by special functions (e.g. time window, collector excess temperature limitation etc.) this is to be especially allowed for when assigning outputs.
Page 31
English You can only enter the status menu if there has been an error. Then, ENTER is displayed instead of OK or CETOFF in Stat. OK appears under Stat if the monitoring functions are activated and the system is running well. If anything special happens, Stat blinks regardless of the display position.
English The menu Men Language Code to enter the Sensor menu menu System protection Start function Solar priority function only displayed for progr. with priority After-running time of Pump speed control Control outputs outputs Function check Heat quantity Legionella- counter function External sensors via Drain-back...
English Brief description Actually chosen menu language = English. Factory settings are ENGL made in DEUT (German). Code to enter the menu. The other menu items are only displayed once the correct CODE code has been entered. Sensor settings: selection of sensor type, SENSOR mean value of sensor values and assignment of icons for sensors.
English Troubleshooting In general, all of the settings in the menus Par and Men and the terminals should be checked if there is an error. Malfunction, but “realistic” temperatures: Check the program number. Check the thresholds for on/off and the set differential temperatures. Have the thermostat and differential thresholds been reached? ...
English Table of settings If the control system fails unexpectedly, all of the settings should be reset for initial configuration. In this case, problems are inevitable if all of the setting values are entered in the following table. If there are questions, this table has to be provided. Only then is a simulation possible to reproduce the error.
Francais Prescriptions en matière de sécurité La présente notice s'adresse exclusivement à un personnel spécialisé autorisé.Veillez à ce que le régulateur ne soit pas sous tension lors de la réalisation des travaux de montage et de câblage. Seul un personnel compétent est autorisé à ouvrir, raccorder et mettre l’appareil en service.
Francais Schémas hydrauliques Vous pouvez télécharger le mode d’emploi complet avec tous les schèmes et programmes de la page Internet: www.ta.co.at domaine DOWNLOADS Systèmes pompes-vannes des programmes 49, 177, 193, 209, 225, 226, 227, 417, 625 : Régulation de la vitesse (si activée) : ...
Francais Programme 320 - Accumulateur à couches et pompe de chargement Le système à plusieurs niveaux n’est efficace qu’avec une régulation de la vitesse activée ! (Régulation de la valeur absolue : RA N1) S5 S5 Réglages nècessaires : min1 min3 <min2 >min2...
Francais Instructions de montage Montage des capteurs L’installation et le montage corrects des capteurs sont d’une importance considérable pour assurer le bon fonctionnement du système. Il faut veiller à ce que les capteurs soient placés entièrement dans une douille plongeuse. Le passe-câble à vis respectif fourni peut servir de décharge de traction. Afin que les capteurs de contact ne subissent pas l’influence de la température ambiante, celles-ci doivent bien être isolées.
Francais Capteur de contact : La meilleure solution consiste à fixer le capteur sur la conduite correspondante au moyen de ressorts enroulés, de colliers de serrage pour tubes ou flexibles. Veiller à utiliser le matériau approprié (corrosion, résistance à la température, etc.). En outre, le capteur doit être bien isolée afin de pouvoir enregistrer la température du tube avec précision et de ne pas être influencée par la température ambiante.
Francais Montage de l’appareil ATTENTION ! ATTENTION ! TOUJOURS DEBRANCHER LA PRISE DU SECTEUR AVANT D’OUVRIR LE BATI ! Tous travaux à l’intérieur du régulateur doivent être effectués hors tension. Desserrer la vis sur le bord supérieur du boîtier et enlever le couvercle. L’électronique de régulation est abritée dans ce couvercle.
Le câble de données bidirectionnel (Bus DL) a été conçu pour la série ESR/UVR et est uniquement compatible avec les produits de la société « Technische Alternative ». Chaque câble d’une section de 0,75 mm² peut servir de câble de données (p. ex. : toron double) jusqu'à une longueur max.
Francais Manipulation Le grand afficheur comporte tous les symboles d’information importants et une zone de texte en clair. La navigation avec les touches de coordonnées est adaptée au déroulement de l’affichage. ...
Francais Le niveau principal Température Température Température Capteur 1 Capteur 2 Capteur 6 Débit volumique Vitesse du vent Valeur externe 1 apparaît uniquement apparaît uniquement Apparaît uniquement lorsque S6 = VSG lorsque S6 = WS lorsque DL externe est activé Valeur externe 9 Fonction protection Niveau régulation...
Page 50
Francais T1 à T6 Affiche la valeur mesurée au captur (S1 – T1, S2 – T2, etc.) L’affichage (unité) dépend du réglage du type de capteur. Types d’affichage : Température en °C Rayonnement en Etat numérique (Capteurs KTY, (Capteur de (entrée numérique) PT1000, ou rayonnement)
Francais Affichage de l’état de l’installation (Status). Selon le programme sélectionné, différents Stat: états de l’installation sont surveillés. Ce menu contient toutes les informations relatives aux éventuels problèmes (survenus). Au niveau du paramétrage, les touches de navigation (,) servent à sélectionner les Par: symboles en dessous de l’affichage de la température et de la ligne du texte.
Francais Le menu Paramètres Par Numéro de code p. Numéro de la Numéro de accéder au menu version programme Changer des sorties Assignation de Limitation maximale priorité n’est affichée du seuil d’arrêt (3 que pour les progr. fois) avec priorité Limitation max.
Francais Attribution des sorties Automatique / Mode Automatique / mode libres manuel (3 fois) manuel (2 fois) pour (selon le schéma) pour les sorties 1-3 les sorties de commande Description sommaire Numéro de code pour accéder au menu. Les autres menus ne sont affichés que quand CODE l’entrée du numéro de code correcte a été...
Francais Numéro de code pour Numéro de la Numéro de accéder au menu version Programme Numéro de code CODE Uniquement après saisie du bon numéro de code (numéro de code 32), les autres points de menu du menu de paramétrage apparaissent. Version du logiciel VER Affichage de la version du logiciel.
Francais Assignation de priorité AP Pour les schémas de programmes à plusieurs récepteurs pour un générateur, on peut effectuer un réglage par Assignation de Priorité. Ce menu est uniquement affiché pour des schémas de programmes avec priorité. L’ordre de priorité (sorties concernées) est adapté...
Page 56
Francais Exemple : Numéro de programme 0 Limitation max. du Limitation max. du Limitation min. du seuil de mise à l’arrêt seuil de mise en seuil de mise en marche marche Limitation min. du Différence seuil de Différence seuil de seuil de mise à...
Francais Heure Exemple : 16:34 = Indication de l’heure Le réglage de l’heure est effectué par simple pression sur la touche d’entrée et sur les touches de navigation. Par une nouvelle pression sur les touches on peut passer des minutes aux heures et vice-versa. Heure ATTENTION ! Même si les fenêtres horaires ne sont pas utilisées, le réglage correct de la date et de l’heure peut se révéler judicieux.
Francais Numéro de la plage horaire Sorties attribuées Durée de Temps de blocage l’autorisation Dans l’exemple, la sortie 1 est attribuée à la masque de temps 1 (indexe). La mise en marche de la sortie est autorisée dans la plage horaire de 6 :30 à 21 :30 heures. Les sorties suivantes sont attribuées à...
Francais Dans l’exemple, la fonction minuterie est attribuée à la sortie 1. La sortie est autorisée pendant 5 heures et bloquée pendant 2 heures. Les sorties suivantes sont attribuées à la fonction minuterie. (RU = --) A (ET) Pendant la durée d'autorisation, le programme détermine le statut des sorties sélectionnées.
Francais ATTENTION : La fonction de commutation ne se réfère pas directement à la sortie affectée, mais uniquement à sa fonction dans le diagramme du programme. Une attribution prioritaire n'est pas prise en compte. Si la sortie doit également être influencée par des fonctions spéciales (p. ex. fenêtre horaire, limitation de surchauffe du collecteur etc.), il convient alors d'y accorder une attention particulière lors de l'attribution des sorties de ces fonctions.
Page 61
Francais Les messages d’erreurs (et Stat clignote) restent affichés même après la disparition de l’erreur et doivent être supprimés dans le menu d’état via la commande CLEAR. On ne peut accéder au menu d’état que si une erreur s’est produite. Alors ENTER apparaît sous Stat, au lieu de OK, respectivement ETC DE.
Francais Le menu Men Sélection de langue Numéro de code Menu SENSOR pour accéder au (capteur) menu Fonction de Fonction de La priorité solaire, protection de démarrage uniquement affichée l’installation p. programmes à priorité Temps de marche à Régulation vitesse Sorties de commande vide des sorties pompe...
Francais Description sommaire Langue de menu actuellement sélectionnée = international. Le réglage usine se INTER fait en langue allemande. Numéro de code pour accéder au menu. Les autres menus ne sont affichés que quand CODE l’entrée du numéro de code correcte a été affichée. Réglages du capteur (senseur): Sélection du type de capteur SENSOR Formation de valeurs moyennes capteur...
Francais Consignes en cas de panne Si vous soupçonnez un dysfonctionnement, il faut généralement commencer par vérifier tous les paramètres des menus Par et Men ainsi que le branchement. Dysfonctionnement, mais valeurs de température « réalistes » : Contrôle du numéro de programme. ...
Francais Tableau des réglages Si la commande tombe inopinément en panne, vous devrez alors répéter toute la procédure de réglage lors de la remise en service. Dans un tel cas, des problèmes peuvent être évités si toutes les valeurs de réglage ont été notées dans le tableau ci-dessous. En cas de questions, vous devez impérativement le communiquer.
EU Declaration of conformity Document- Nr. / Date: TA17004 / 02/02/2017 Company / Manufacturer: Technische Alternative RT GmbH Address: A- 3872 Amaliendorf, Langestraße 124 This declaration of conformity is issued under the sole responsibility of the manufacturer. Product name: UVR61-3, UVR61-3-PV...
Legal notice These assembly and operating instructions are protected by copyright. Use outside the copyright requires the consent of the company Technische Alternative RT GmbH This applies in particular to reproductions, translations and electronic media.
Remarque : Les conditions de garantie suivantes ne se limitent pas au droit légal de garantie mais élargissent vos droits en tant que consommateur. 1. La société Technische Alternative RT GmbH accorde une garantie de deux ans à compter de la date d'achat au consommateur final sur tous les produits et pièces qu'elle commercialise.