Program 176 - Solar power system with 2 consumers and feed pump function

S1
A2
A1
S2
S1
min1
diff1
diff2
A1
A2
S2
S3
max1
max2
Program 176: Pump A1 runs when:
 S1 is greater than the threshold min1  and S1 is greater than S2 by the difference diff1
 and S2 has not exceeded the threshold max1.
Pump A2 runs when:
 S1 is greater than the threshold min1  and S1 is greater than S3 by the difference diff2
 and S3 has not exceeded the threshold max2.
The feed pump A3 runs when:
 S5 is greater than the threshold min2  and S5 is greater than S4 by the difference diff3
 and S4 has not exceeded the threshold max3.
All programs +1: Instead of both pumps A1 and A2 one pump A1 and a three-way valve A2 are
deployed. Speed control: Observe the comments on page 7!
Without a priority allocation, tank 2 is filled by priority.
A1 ... common pump
All programs +2: When both tanks have reached their maximum temperature via the solar system,
the pumps A1 and A3 are switched on (re-cooling function).
All programs +4: Both solar circuits have separate switch-on thresholds on S1.
The output A1 continues to retain min1 and A2 switches with min3.
All programs +8: The limiting of tank TK1 is made via the independent sensor S6 and the maximum
threshold max1 (no more maximum threshold on S2)
The priorities for TK1 and TK2 can be set in the parameter menu under PA. In addition, a solar
priority function can be set for this diagram in the menu PRIOR.
10
SP1
TK1
S4
A3
S4
S5
required settings:
min2
max1 ... limit TK1 S2
max2 ... limit TK2 S3
max3 ... limit TK1 S4
diff3
min1 ... switch-on temp. coll. S1
A3
min2 ... switch-on temp. TK2 S5
min3 ... see all programs +4
diff1
S4
diff2
max3
diff3
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2
A3 = S5 > (S4 + diff3) & S5 > min2 & S4 < max3
A2 ... Valve (A2/S receives power when filling tank TK2)
SP2
TK2
S5
S3
... coll. S1 – TK1 S2
... coll. S1 – TK2 S3
... TK2 S5 – TK1 S4
 A1
 A2
 A3
 A1, A2
 A3
 A1
 A2
 A3