Diagramme de dépannage n° 6
DIAGRAMME 5
CHART 5
YES
RÉGLER LA TEMPÉRATURE SOUS LE
SET THERMOSTAT BELOW ROOM
POINT DE CONSIGNE DE LA PIÈCE
TEMPERATURE TO END CALL FOR
POUR METTRE FIN À LA DEMANDE DE
HEAT
CHALEUR.
YES
OUI
LE CIRCULATEUR S'ARRÊTE-T-IL?
DOES CIRCULATOR PUMP STOP?
YES
OUI
LE VOYANT DE LA SOUPAPE EST ÉTEINT
VALE LIGHT IS OFF
YES
OUI
LE VENTILATEUR À TIRAGE S'ARRÊTE-
DOES DRAFT BLOWER
T-IL APRÈS LE POSTBALAYAGE DE
STOP AFTER 30
SECOND POST PURGE?
30 SECONDES?
OUI
YES
LE SYSTÈME FONCTIONNE
SYSTEM OK
DIAGRAMME 5
CHART 5
OUI
NUMÉRO 3
NO #3
LA CHAUDIÈRE S'ÉTEINT AVANT LA FIN
BOILER SHUTS OFF BEFORE END OF
DE LA DEMANDE DE CHALEUR. LES
CALL FOR HEAT. ARE HI LIMIT
CONTACTS DE L'INTERRUPTEUR DE
AQUASTAT CONTACTS CLOSED?
LIMITE SUPÉRIEURE SONT-ILS FERMÉS?
YES
OUI
VOIR LE CHEMINEMENT DE DÉPANNAGE
SEE TROUBLESHOOTING PATH
NO2 CI-DESSUS
#2 ABOVE
NO
NON
LES CONTACTS DU THERMOSTAT SONT-
ARE THERMOSTAT CONTACTS OPEN?
REMPLACER LA COMMANDE INTÉGRÉE
DE LA CHAUDIÈRE
REMOVE WIRING HARNESS
DÉBRANCHER LE FAISCEAU DE
NON
NO
CÂBLAGE CN9 DE LA SOUPAPE DE
CONNECTION CN9 FROM GAS
COMMANDE DE GAZ, LA SOUPAPE
CONTROL DOES GAS CONTROL
COMMANDE DE GAZ SE FERME-T-ELLE?
NON
NO
REMPLACER LA COMMANDE INTÉGRÉE
DE LA CHAUDIÈRE
15 - DÉPANNAGE
CHART 5
DIAGRAMME 5
NO #2
NUMÉRO 2
FONCTIONNE PENDANT 25 À 50 SECONDES,
RUNS FOR 25-50 SECONDS,
THEN TURNS OFF.
PUIS S'ÉTEINT.
VÉRIFIER LE TAUX D'ALLUMAGE DE
CHECK FIRING RATE OF UNIT.
L'APPAREIL.
IS UNIT FIRING AT THE CORRECT RATE?
L'APPAREIL S'ALLUME-T-IL AU BON TAUX?
OUI
YES
INSPECTER LE BRÛLEUR POUR Y DÉTECTER
CHECK BURNER FOR ANY DETERIORATION
LA PRÉSENCE DE DÉTÉRIORATION DES
IN THE FLAME PORTS. ARE BURNER PORTS
ORIFICES DE FLAMME. LES ORIFICES DU
IN GOOD CONDITION.
BRÛLEUR SONT-ILS EN BON ÉTAT?
OUI
YES
VÉRIFIER SI LE SIGNAL DE FLAMME
CHECK FLAME SIGNAL > 0.6uA?
EST >0.6uA?
CONSULT BOILER MFGR. FOR
CONSULTER LE FABRICANT DE
SPECIFIC INSTRUCTIONS. REQUIRES
LA CHAUDIÈRE POUR OBTENIR DES
SPECIFIC TOOLS.
DIRECTIVES PRÉCISES. NÉCESSITE
DES OUTILS PARTICULIERS.
LA CHAUDIÈRE S'ÉTEINT LORSQUE
LA TEMPÉRATURE ATTEINT LA LIMITE
BOILER OFF ON HIGH LIMIT. IS
SUPÉRIEURE. LA TEMPÉRATURE RÉELLE
NON
NO
ACTUAL BOILER WATER TEMP.
DE L'EAU DE LA CHAUDIÈRE EST-ELLE
GREATER THAN HI LIMIT SET POINT
SUPÉRIEURE AU POINT DE CONSIGNE
MINUS 30°F CONTROL DIFFERENTIAL?
DE LIMITE SUPÉRIEURE MOINS LE
DIFFÉRENTIEL DE 30 °F?
NON
NO
ILS OUVERTS?
OUI
YES
REPLACE IBC
NON
NO
CLOSE?
YES
OUI
REPLACE IBC
40
REMPLACER LA SOUPAPE DE
REPLACE GAS CONTROL.
COMMANDE DE GAZ.
OUI
YES
VÉRIFIER LA DIMENSION D'ADMISSION DU GAZ.
CHECK GAS ORFICICE SIZE.
L'ORIFICE D'ADMISSION DU GAZ EST-IL DE LA
IS GAS ORIFICE SIZE CORRECT.
BONNE DIMENSION? VÉRIFIER LA LISTE DES
CHECK REPAIR PARTS LIST
PIÈCES DE RECHANGE POUR Y TROUVER LA
FOR CORRECT SIZE. IS GAS ORIFICE
BONNE DIMENSION. L'ORIFICE D'ADMISSION DU
CLEAR OF BLOCKAGE.
GAZ EST-IL LIBRE DE TOUTE OBSTRUCTION?
OUI
YES
NON
NO
L'APPAREIL EST-IL ALIMENTÉ AU GAZ
DOES THE UNIT USE LP GAS.
PROPANE LIQUIDE?
NO
NON
RÉGLER LE TAUX TEL QU'EXPLIQUÉ
ADJUST RATE AS DESCRIBED IN THE
DANS LA RUBRIQUE « PROCÉDURE DE
CHECK OUT PROCEDURE AND
VÉRIFICATION ET DE RÉGLAGE » DU
ADJUSTMENT SECTION
OF THE MANUAL.
MANUEL.
NO
NON
REMPLACER PAR UN DÉFLECTEUR D'AIR
REPLACE WITH CORRECT
AIR BAFFLE.
ADÉQUAT.
NON
NO
REMPLACER LE BRÛLEUR
REPLACE BURNER
YES
OUI
REMPLACER LA COMMANDE INTÉGRÉE
REPLACE IBC
DE LA CHAUDIÈRE
NO
NON
NON
NO
REMPLACER LE THERMOSTAT
REPLACE THERMOSTAT
REMPLACER LA SOUPAPE
REPLACE GAS CONTROL
DE COMMANDE DE GAZ.
REPLACE
OK
AQUASTAT
OK
OK