Diagramme de dépannage n° 4
DIAGRAMME 3
CHART 3
OUI
YES
LE DISPOSITIF D'ALLUMAGE/
IGNITER/SENSOR WARMS
CAPTEUR RÉCHAUFFE
UP AND GLOWS
ET PRODUIT UNE LUEUR
YELLOW/ORANGE
JAUNE/ORANGÉE
DURING 20 SECOND
DURANT 20 SECONDES
WARM UP
RÉCHAUFFEMENT
OUI
YES
APRÈS UN RÉCHAUFFEMENT
DE 20 SECONDES DU
AFTER 20 SECOND
DISPOSITIF D'ALLUMAGE, LA
IGNITER WARM UP, GAS
SOUPAPE DE GAZ EST MISE
VALVE IS ENERGIZED
SOUS TENSIONLE VOYANT
VALVE LIGHT IS ON
DE LA SOUPAPE S'ALLUME
2 SECONDS LATER POWER
2 SECONDES PLUS TARD,
IS REMOVED FROM
L'ALIMENTATION DU
IGNITER/SENSOR
DISPOSITIF D'ALLUMAGE/
CAPTEUR EST COUPÉE
IGNITER LIGHT IS OFF
LE VOYANT DU DISPOSITIF
DOES MAIN BURNER
D'ALLUMAGE EST ÉTEINT
LIGHT?
LE BRÛLEUR PRINCIPAL
S'ALLUME-T-IL?
OUI
YES
DIAGRAMME 5
CHART 5
15 - DÉPANNAGE
VÉRIFIER LE 120 V CA ENTRE
CHECK FOR 120 VAC
LES BORNES 1 ET 2 AU
BETWEEN TERMINALS 1
NON
NO
CONNECTEUR CN1 DE LA
AND 2 AT CONNECTOR
COMMANDE INTÉGRÉE DE
LA CHAUDIÈRE (DURANT
CN1 ON IBC (DURING
LE RÉCHAUFFEMENT DU
IGNITER WARM UP)
DISPOSITIF D'ALLUMAGE)
YES
OUI
CHECK FOR 120 VAC AT
VÉRIFIER LE 120 V CA
IGNITER/SENSOR LEADS
AUX FILS DU DISPOSITIF
D'ALLUMAGE/CAPTEUR DU
ON WIRING HARNESS
FAISCEAU DE CÂBLAGE
(DURING IGNITER
(DURANT LE RÉCHAUFFEMENT
WARM UP)
DU DISPOSITIF D'ALLUMAGE)
YES
OUI
VÉRIFIER LE 24 V CA À
CHECK FOR 24 VAC
TRAVERS LES BORNES MV
ACROSS TERMINALS MV
NON
NO
DE LA COMMANDE DE GAZ.
ON THE GAS CONTROL.
PENDANT QUE LE VOYANT
WHILE VALVE/FLAME
DEL DE LA SOUPAPE/FLAMME
INDICATOR LIGHT IS ON
EST ALLUMÉ
OUI
YES
VÉRIFIER SI LE DISPOSITIF
CHECK IF IGNITER/
D'ALLUMAGE/CAPTEUR EST
SENSOR POSITION IS OK?
À LA BONNE POSITION?
TIP SHOULD BE SLANTED
LA POINTE DEVRAIT ÊTRE
TOWARDS BURNER
INCLINÉE VERS LE BRÛLEUR
OUI
YES
CHECK GAS SUPPLY
VÉRIFIER SI LA PRESSION
PRESSURE AT INLET
DE L'APPROVISIONNEMENT
PRESSURE TAPPING ON
EN GAZ AU NIVEAU DE
L'ORIFICE DE PRESSION DE
GAS CONTROL IS GAS
LA COMMANDE DE GAZ EST
PRESSURE GREATER
SUPÉRIEURE À 4,0 POUCES
THAN 4.0" W.C.?
DE COLONNE D'EAU (1KPA).
YES
OUI
DIAGRAMME 5
CHART 5
NON
NO
REMPLACER LA COMMANDE
REPLACE IBC
INTÉGRÉE DE LA CHAUDIÈRE
RÉPARER/REMPLACER LE
CÂBLAGE DE LA COMMANDE
REPAIR/REPLACE WIRING
NON
NO
INTÉGRÉE DE LA CHAUDIÈRE
FROM IBC
VERS LE DISPOSITIF
TO IGNITER/SENSOR
D'ALLUMAGE/ CAPTEUR
REMPLACER LE DISPOSITIF
REPLACE IGNITER/SENSOR
D'ALLUMAGE/ CAPTEUR
VÉRIFIER LE 24 V CA À
TRAVERS LES BORNES CN6-2
CHECK FOR 24 VAC
ET CN6-5 DE LA COMMANDE
ACROSS TERMINALS
NO
NON
INTÉGRÉE DE LA CHAUDIÈRE,
CN6-2 AND CN6-5 ON
PENDANT QUE LE VOYANT
IBC, WHILE THE VALVE/
DEL DE LA SOUPAPE/FLAMME
FLAME LED IS LIT
EST ALLUMÉ
YES
OUI
REPAIR/REPLACE WIRING
RÉPARER/REMPLACER
BETWEEN IBC AND
LE CÂBLAGE ENTRE
LA COMMANDE INTÉGRÉE
GAS CONTROL
DE LA CHAUDIÈRE ET
LA COMMANDE DE GAZ
REMETTRE LE DISPOSITIF
RESTORE IGNITER/SENSOR
NON
NO
D'ALLUMAGE/CAPTEUR
TO CORRECT POSITION.
À LA BONNE POSITION. NE
DO NOT RELOCATE
PAS CHANGER LA POSITION
TOUS LES DISPOSITIFS
ARE ALL MANUAL
D'ARRÊT MANUEL
SHUT-OFFS IN THE GAS
NON
DE LA CONDUITE
NO
SUPPLY LINE AND ON
D'ALIMENTATION EN GAZ
THE GAS CONTROL IN
ET DE LA COMMANDE DE
THE OPEN OR ON
GAZ SONT-ILS EN POSITION
POSITION?
OUVERTE OU « MARCHE »?
OUI
YES
CONTACTER LE SERVICE DE
CONTACT THE GAS UTILITY
GAZ POUR OUVRIR LE GAZ
TO TURN THE GAS ON
38
NON
NO
REMPLACER LA COMMANDE
REPLACE IBC
INTÉGRÉE DE LA CHAUDIÈRE
OUVRIR OU METTRE TOUS
NON
NO
OPEN OR TURN ON ALL
LES DISPOSITIFS D'ARRÊT
MANUAL SHUTOFFS
MANUEL EN MARCHE