Start-Up And Operation; Preliminary Checks; Start-Up; Preventive Maintenance - Pratissoli HF Série Manuel D'utilisation Et D'entretien

Masquer les pouces Voir aussi pour HF Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 41
10

START-UP AND OPERATION

10.1

Preliminary checks

Before start-up, ensure that:
The suction line is connected and pressurised
(see par. 9.4 - 9.5 - 9.6) the pump must never run
dry.
1. The suction line ensures a hermetic seal over time.
2. Any shut-off valves between the supply source and
the pump are fully open. The outlet line during is free
discharge, to permit air present in the pump head to come
out quickly and therefore favour fast priming.
3. All suction and outlet fittings and connections are
properly tightened.
4. The coupling tolerances on the pump/transmission axis
(half-joint misalignment, Cardan joint tilt, belt pulling,
etc.) remain within limits required by the transmission
manufacturer.
5. Oil in the pump casing is at level, verified with a dipstick
(Fig. 14, pos. ) and exceptionally with a level indicator
(Fig. 14, pos. ).
In case of prolonged storage or long-term
inactivity, check proper functioning of the
suction and outlet valves.
10.2

Start-up

1. At first start-up, verify that the rotation direction and the
supply pressure are correct.
2. Start-up the pump without any load.
3. Check that the supply pressure is correct.
4. Check that the rotation rpm during operation does not
exceed the nominal rpm of the pump.
5. Let the pump run for a period of no less than 3 minutes,
before putting it under pressure.
6. Before each pump stop, reset pressure by means of the
control valve or with any relieving devices and reduce to a
minimum rpm (activation with combustion motors).
11

PREVENTIVE MAINTENANCE

For pump reliability and efficiency, comply with maintenance
intervals as shown in the table of Fig. 15.
PREVENTIVE MAINTENANCE
Every 500 hours
Check oil level
12

PUMP STORAGE

12.1

Long-term inactivity

If the pump is started for the first time after a long
period from the date of shipment, before operation
check the oil level, inspect the valves as specified
in chapter 10, then follow described start-up
procedures.
12.2
Method for filling pump with anti-corrosion
emulsion or anti-freeze solution
Method for filling pump with anti-corrosion emulsion or anti-
freeze solution using an external diaphragm pump based on
the layout shown in par. 9.7, between pos.  and pos.  of
Fig. 6 and Fig. 6/a:
In place of the service tank, use a suitable container
containing the solution to be pumped.
Close the filter drainage, if open.
Make sure that the hoses to be used are clean inside and
spread grease on their connections.
Connect the high pressure exhaust pipe to the pump.
Connect the suction pipe to the diaphragm pump.
Connect the suction pipe between the pump head and
Fig. 14
the diaphragm pump.
Fill the service container with solution/emulsion.
Insert the free ends of the suction pipes and the high
pressure exhaust pipe inside the container.
Switch on the diaphragm pump.
Pump the emulsion until it exits from the high pressure
exhaust pipe.
Continue pumping for at least another minute.
Stop the pump and remove the previously connected
pipes.
Clean, grease and plug the connections on the pump
head.
The characteristics of the emulsion can be strengthened if
necessary by adding, for example, Shell Donax.
13

PRECAUTIONS AGAINST FROST

Follow the instructions in Chapter 12 in areas and
times of the year at risk of frost (see par. 12.2).
In the presence of ice, do not run the pump
for any reason until the circuit has been fully
defrosted, in order to avoid serious damage to
the pump.
33
Every 1000 hours
Change oil
Check / Replace:
Valves
Valve seats
Valve springs
Valve guides
Check / Replace:
H.P. seals
L.P. seals
Fig. 15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Wk sérieHf18Hf20Hf22Hf25Hf25n ... Afficher tout

Table des Matières