TECHNICAL DATA

MODEL
TYP
OUTPUT
(1)
DELIVERY
(1)
FUEL
Gas pressure at maximum delivery.
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTORS
FAN MOTOR
(star-delta starting for RLS400)
PUMP MOTOR
IGNITION TRANSFORMER
PUMP
delivery at 25 bar (kg/h)
pressure range (bar)
fuel temperatur (°C max)
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
CONFORMITY TO EEC DIRECTIVES
NOISE LEVELS
(3)
APPROVAL
APPROVAL
Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(1)
Pressure at test point 5)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(2)
Sound pressure measured in manufacturer»s combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3)

ACCESSORIES

(optional)
OUTPUT POWER REGULATOR KIT:
rates between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two compo-
nents should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
• KIT AZL (display and operating unit)
• PRESSURE SWITCH KIT (for leak detection control)
• KIT SOFTWARE INTERFACE
GAS TRAIN ACCORDING TO REGULATION EN 676
Note.
The installer is responsible for the addition of any safety device not forseen in the present manual.
MIN - MAX
kW
kg/h
- Gas: G20/G25
mbar
(2)
number
°C max
rpm
kW
kW
V1 - V2
I1 - I2
kW max
dBA
class 3 (EN 676)
CE
DIN
Under modulating operation, the burner automatically adapts to one of an infinite number of firing
Range
- 100...+ 500°C
0...2,5 bar
0...16 bar
RLS 300/E MX
782 T1
600 ... 3650
50 ... 309
LIGHT OIL, viscosity at 20 °C: 6 mm
NATURAL GAS: G20 (methane) - G21 - G22 - G23 - G25
- Continuous / Intermittent (min. 1 stop in 24 hours)
- Progressive two-stage or modulating by kit (see ACCESSOIRES)
1
Boilers: water, steam, diathermic oil
°C
0 - 40
60
3N ~ 400 / 230V +/-10% 50 Hz
2900
V
230/400
4,5
A
16 - 9
V
A
7,5
IP 54
90/396 - 89/336 - 73/23
80
PROBE
Type
PT 100
Output probe
4...20 mA
Code 3010355
Code 3010344
Code 3010388
: see page 26.
8
RLS 400/E MX
783 T1
800 ... 4300
70 ... 365
2
/s max (1,5 °E - 6 cSt)
2900
400/680
7,5
16 - 9
230/400
1,5
6.4/3.7
230 V - 2 x 5 kV
1,9 A - 35 mA
680
7 - 40
140
11,5
85
POWER REGULATOR
Code
Type
3010110
RWF40 BASIC
3010213
RWF40 HIGH
3010214
Code
3010356
3010357