GB
Do not lose these safety instructions
Technical data
Mains connection
Motor rating W
Operating mode
Compressor speed min
-1
Pressure vessel capacity (in liters)
Operating pressure
Theoretical intake capacity (l/min)
sound power level L
WA
uncertainty K
WA
Protection type
Weight of the unit in kg
The noise emission values were measured in accord-
ance with EN ISO 3744.
Wear hearing protection.
The effects of noise can cause a loss of hearing.
Before starting the equipment
Before you connect the equipment to the mains supply
make sure that the data on the rating plate are identical
to the mains data.
• Check the equipment for damage which may have
occurred in transit. Report any damage immediately
to the transport company which was used to deliver
the compressor.
• Install the compressor near the point of consumption.
• Avoid long air lines and supply lines (extension ca-
bles).
• Make sure that the intake air is dry and dustfree.
• Do not install the compressor in a damp or wet room.
• The compressor may only be used in suitable rooms
(with good ventilation and an ambient temperature from
+5 °C to 40 °C). There must be no dust, acids, vapors,
explosive gases or inflammable gases in the room.
• The compressor is designed to be used in dry rooms.
It is prohibited to use the compressor in areas where
work is conducted with sprayed water.
Attachment and operation
n
Important!
You must fully assemble the appliance before using
it for the first time!
Mains connection
• The compressor is equipped with a mains cable with
shock-proof plug. This can be connected to any 230-
240 V~ 50 Hz shock-proof socket which is protected
by a 16 A fuse.
• Before you use the machine, make sure that the
mains voltage is the same as the operating voltage
(see the rating plate).
16 І 116
230 V~ 50 Hz
max. 1100
S1
3750 min
-1
2
approx. 8 bar
approx. 180
95 dB(A)
3 dB
IP20
8
• Long supply cables, extensions, cable reels etc.
cause a drop in voltage and can impede motor start-
up.
• At low temperatures below +5°C, sluggishness may
make starting difficult or impossible.
ON/OFF switch (fig. 1)
• To switch on the compressor, press the button (2) on
position I.
• To switch off the compressor, press the button (2) on
position 0.
Setting the pressure (Fig. 1)
• Use the pressure regulator (8) to set the pressure on
the pressure gauge (7).
• The set pressure can be drawn from the quicklock
coupling (6).
• The vessel pressure can be read off the pressure
gauge (4).
Setting the pressure switch
• The pressure switch is set at the factory.
Cut-in pressure approx. 6 bar.
Cut-out pressure approx. 8 bar.
m Important!
The accessories used must be adapted to the
maximum allowable pressure of the mobile com-
pressor
Use pressure hoses with safety cable (eg wire
rope)
Electrical connection
The electrical motor installed is connected and
ready for operation. The connection complies with
the applicable VDE and DIN provisions.
The customer's mains connection as well as the
extension cable used must also comply with these
regulations.
Damaged electrical connection cable
The insulation on electrical connection cables is often
damaged.
This may have the following causes:
• Passage points, where connection cables are passed
through windows or doors.
• Kinks where the connection cable has been improp-
erly fastened or routed.
• Places where the connection cables have been cut
due to being driven over.
• Insulation damage due to being ripped out of the wall
outlet.
• Cracks due to the insulation ageing.
Such damaged electrical connection cables must not be
used and are life-threatening due to the insulation damage.
Check the electrical connection cables for damage reg-
ularly. Make sure that the connection cable does not
hang on the power network during the inspection.
Electrical connection cables must comply with the ap-
plicable VDE and DIN provisions. Only use connection
cables with the marking „H05VV-F".