Control Panel - Camille Bauer KINAX WT720 Mode D'emploi

Masquer les pouces Voir aussi pour KINAX WT720:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

10. Programming instruction

10.1 Control panel

The transmitter is programmable via switch and push-button.
These will be visible after opening the top cover.
Pressure-time for programming:
short = 0.1s
long = 1s
Programming within EX Zones 1 and 2 is
permitted, but not in EX Zones 21 and 22.
10.2 Programming "Linear curve"
1.
Turn the switch to the linear mode (DIP2 „off")
2.
Choose rotary sense:
3.
Programming mode „on"
3 x short „0%" (0%; 0%; 0% → LED lights permanently)
4.
Bring transmitter to the starting position
Programming 0%
1 x short „0%" (0% → LED flashes shortly 1 x)
5.
Bring transmitter to the end position
Programming 100%
1 x short „100%" (100% → LED flashes shortly 1 x)
6.
Programming mode „off"
3 x short „0%" ( → LED lights are no longer)
The zeropoint of a factory programmed linear curve can be
shifted, if point 1-4 and 6 of the programming instruction
programming "linear curve" are followed.
If there is in programming mode for about 15 minutes no
button pressed, the programming mode will be closed au-
tomatically without saving the changed parameters.
10.3 Programming "V-characteristic"
I
out
vmax1
20 mA
4 mA
vmin1
vmin2
Rotation clockwise
It is important to note that the points vmax1, vmin1, vmin2,
vmax2 has to turn clockwise!
1.
Turn the switch to the linear mode (DIP2 „on")
2.
Programming mode „on"
3 x short „0%" (0%; 0%; 0% → LED lights permanently)
3.
Bring transmitter in position „vmax1" of the V-characte-
ristic
Programming vmax1
1 x short „100%" (100% → LED flashes shortly 1 x)
DIP1 „off"; Clockwise
DIP1 „on"; Counterclockwise
vmax2
Angular
position
4.
Bring transmitter in position „vmin1"
Programming vmin1
1 x short „0%" (0% → LED flashes shortly 1 x)
5.
Bring transmitter in position „vmin2" of the V-characte-
ristic
Programming vmin2
1 x long „0%" (0% → LED flashes shortly 2 x)
6.
Bring transmitter in position „vmax2"
Programming vmax2
1 x long „100%" (100% → LED flashes shortly 2 x)
7.
Programming mode „off"
3 x short „0%" (→ LED lights are no longer)
The zeropoint of a factory programmed V-characteristic can
be shifted, if point 1-3 and 7 of the programming instruction
programming "V-characteristic" are followed.
If there is in programming mode for about 15 minutes no
button pressed, the programming mode will be closed au-
tomatically without saving the changed parameters!
10.4 Restoring the factory default setting (Reset)
1.
Programming mode „on"
3 x short „0%" (0%; 0%; 0% → LED lights permanently)
2.
Push button „0%" for at least 5 s
(0% → LED flashes shortly 5 x; transmitter restart)
15