The backwashing process is triggered primarily
by differential pressure.
If heavy soiling of the filter element causes the
pressure difference to exceed the preset value
(approx. 0.8 bar) within the preset backwash in-
terval, the differential pressure generator causes
the unit to backwash. The preset backwash inter-
val starts again.
The filter is equipped with a central instrumenta-
tion and control (CIC) connection (contact closes
in the event of malfunction or power failure).
Preliminary installation
Preliminary installation
Preliminary installation
Preliminary installation
Preliminary installation
conditions
conditions
conditions
conditions
conditions
Local plumbing codes, general guidelines and the
technical data must be observed.
The system must be installed by the water supply
utility or a plumbing company approved by the water
supply utility in accordance with these installation
and operating instructions and the applicable
regulations.
The installation site must be frostproof and ensure
that the filter is protected from solvent vapours,
heating oil, lees, acidic cleaners, chemicals of all
kinds, direct UV radiation and heat over 40 °C.
A separate power socket (230 V AC, 50 Hz) within a
distance of approx. 1.2 m is required. The power supply
must be permanently ensured. Voltage peaks over 1
kV must be avoided.
If the water contains dirt particles > 2 mm, a coarse
dirt trap must be installed upstream from the filter.
min. DN 50
min. DN 50
min. DN 50
min. DN 50
min. DN 50
A flushing water quantity of at least 1.4 l/s (5 m³/h)
must be available for backwashing.
A drainage connection (min. DN 50) must be available
for discharge of the rinsing water.
Avoid extreme pressure surges (caused, for example,
by downstream solenoid valves or similar).