11.2 Navigation Buttons
4 buttons are provided for navigating in the menu: 3 buttons under the display and 1 at the side. The buttons
under the display are called active buttons and the one at the side is called hidden button.
Each page of the menu is made in such a way as to indicate the function associated with the 3 active buttons
(the ones under the display).
11.3 Warning Lights
Yellow light:
System live signal.
If lit, it means that the system is live.
Red light:
Warning of an alarm/malfunction present in the system.
If the light is blinking it is a non-blocking alarm and the pump can still be controlled. If the
light is fixed it is a blocking alarm and the pump cannot be controlled.
Green light:
Pump ON/OFF signal.
if lit, the pump is running. If off, the pump is stopped.
12.
MENUS
EVOPLUS circulators offer 2 menus: user menu and advanced menu.
The user menu is accessible from the Home Page by pressing and releasing the central "Menu" button.
The user menu is accessible from the Home Page by holding down the central "Menu" button for 5 seconds.
Below are shown the user menu pages with which it is possible to check the system status and modify its
settings.
Instead on the advanced menu there are the configuration parameters for communication with MODBUS
systems (for further details visit the link: http://www.dabpump.it/evoplus). To leave the advanced menu
you must scroll through all the parameters using the central button.
If the menu pages show a key at bottom left it means that it is not possible to change the settings. To
unblock the menus go to the Home Page and press the hidden button and the button under the key at the
same time until the key disappears.
If no button is pressed for 60 minutes, the settings are automatically blocked and the display
switches off. When any button is pressed the display lights up again and the "Home Page" appears.
To navigate in the menus, press the central button.
To return to the previous page, hold down the hidden button, then press and release the central button.
To modify the settings use the left and right buttons.
To confirm the change of a setting, hold down the central button "OK" for 3 seconds. Confirmation will
be indicated by the following icon:
ENGLISH
Never remove the cover if the yellow light is lit.
39