G
EtherCAT P | Configuration (pressure)
MODULE PRESSURE XD ( PDO )
Object
DataType
0x1An0
MODULE PRESSURE XD ( SDO )
Object
DataType
0x60n0
0x80n0
BIT2
STRING (8)
REAL
REAL
BIT2
0x80n1
UINT
USINT
0x90n0
STRING (20)
0x90n1
STRING (8)
Function types
Brands
Type
1
Rosenberg, Comefri,
Gebhardt, Nicotra
2
Ziehl-Abegg,
EBM Papst
3
Fläkt Woods
Description of MODULE PRESSURE XD
The TxPDO Derived Value (equivalent to the data point 0x60n0) provides the volume flow determined from the differential pressure.
The configuration object Volume Flow Display ( 0x80n0 ) sets the display behaviour of the bar graph and LCD. In this case, the value
range of the bar graph can be defined using the start point Bar Graph Minimum Value and the end point Bar Graph Maximum Value,
and its colour (standard white) edited. Refer to the bar graph module for the colours Level OK, Level WARN and Level ERR. If it is not
available, green, yellow and red are used as specified colours. A system-specific display text (7 characters) for the lower line can also
be specified.
In the Volume Flow Configuration ( 0x80n1 ) object, the K-value and the calculation formula for calculating the volume flow
from the differential pressure are defined.
The Volume Flow Description ( 0x90n0 ) object contains the module description in text form, the Volume Flow Unit ( 0x90n1 )
object displays the measurand unit.
Name
Derived Values
Volume Flow Value
Name
Derived Values
Volume Flow Value
Volume Flow Display
Display Mode
Display Lower Line
Bargraph Minimum Value
Bargraph Maximum Value
Bargraph Color
Volume Flow Configuration
K-Factor
Formula Number
Volume Flow Description
Volume Flow Unit
Calculation formula for Volume Flow Configuration ( 0x80n1 )
Description
Description
Computed values
Volume flow rate
Volume flow config
0: No display
1: LCD display
2: LCD & BARGRAPH UNI
3: LCD & BARGRAPH BI
Lower line of text
Bar graph initial value
Bar graph final value
0: white
1: Colour Level OK
2: Colour Level WARNING
3: Colour Level ERROR
Historical data
K-Factor 1...3000
Calculation formula type 1..3
'Device Volume Flow' information text
Information text unit depends on formula
32
PDO
TxPDO
SDO
SDO
SDO
SDO
SDO
SDO
3
= Volume flow [m
/h]
= k-Factor
= Differential pressure
of the static pressures [Pa]
= Air density [kg/m
3
]