6.4 Maximum cable lengths for electronic circuits supplied with 12V DC.
(Wire type SYT1 shielded)
Number of Cells
Consumption (mA)
Wire
0,6 mm
/ 0.02 in
0,9 mm
/ 0.4 in
1,4 mm
/ 0.06 in
1,8 mm
/ 0.07 in
2,3 mm
/ 0.09 in
2,8 mm
/ 0.11 in
6.5 Maximum cable lengths for heating with 12V AC-DC.
(Wire type SYT1 shielded)
Number of Cells
Consumption (mA)
Wire
0,6 mm
/ 0.02 in
0,9 mm
/ 0.4 in
1,4 mm
/ 0.06 in
1,8 mm
/ 0.07 in
2,3 mm
/ 0.09 in
2,8 mm
/ 0.11 in
Note : When using the same cable to supply power to several components, the indicated distances are
divided by the number of connected components.
When using several wires with the same section in parallel by polarity, the indicated distances are
multiplied by the number of connected wires.
2 Cells
40
Wire
section
0,3 (mm²)
188 m
/ 23 AWG
/ 0,12 mi
0,6 (mm²)
422 m
/ 20 AWG
/ 0.26 mi
1,5 (mm²)
940 m
/ 16 AWG
/ 0.58 mi
2,5 (mm²)
1566 m
/ 14 AWG
/ 0.97 mi
4 (mm²)
2526 m
/ 11 AWG
/ 1.57 mi
6 (mm²)
3788 m
/ 10 AWG
/ 2.35 mi
2 Cells
200
Wire
section
0,3 (mm²)
38 m
/ 23 AWG
0.02 mi
0,6 (mm²)
84 m
/ 20 AWG
0.05 mi
1,5 (mm²)
188 m
/ 16 AWG
0.12 mi
2,5 v
314 m
/ 14 AWG
0.2 mi
4 (mm²)
506 m
/ 11 AWG
0.31 mi
6 (mm²)
758 m
/ 10 AWG
0.47 mi
MIRIS 3000/3100
4 Cells
6 Cells
80
120
Maximum cable lengths
94 m
63 m
/ 0.06 mi
/ 0.04 mi
211 m
141 m
/ 0.13 mi
/ 0.09 mi
470 m
313 m
/ 0.29 mi
/ 0.19 mi
783 m
522 m
/ 0.49 mi
/ 0.32 mi
1263 m
842 m
/ 0.78 mi
/ 0.52 mi
1894 m
1263 m
/ 1.18 mi
/ 0.78 mi
Heater MIRIS 3000/3100
4 Cells
6 Cells
400
600
Maximum cable lengths
19 m
12 m
0.01 mi
39.37 ft
42 m
28 m
0.03 mi
0.02 mi
94 m
63 m
0.06 mi
0.04 mi
157 m
104 m
0.1 mi
0.06 mi
253 m
168 m
0.16 mi
0.1 mi
379 m
254 m
0.24 mi
0.16 mi
- 44 -
MIRIS 3000 / 3100
8 Cells
160
47 m
/ 0.03 mi
106 m
/ 0.07 mi
235 m
/ 15 mi
392 m
/ 0.24 mi
632 m
/ 0.39 mi
947 m
/ 0.59 mi
8 Cells
800
9 m
29.53 ft
27 m
0.02 mi
47 m
0.03 mi
78 m
0.05 mi
126 m
0.08 mi
189 m
0.12 mi