Optimization Of Alignment - SORHEA MIRIS 3000 Notice D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SORHEA
7.2

Optimization of alignment

"Master" Control Unit:
Switches 1 and 2:
Channel selection
Push button "SELECT":
1. Connect the column modules to main power.
The red led blinks for 5 to 10 seconds during the start-up phase of the column.
2. Push the "SELECT" button of the Control Unit (for at least 2 seconds) until the buzzer of the
Master module beeps twice.
The red led blinks once and the buzzer emits a long beep on the Master module showing that the
bottom cell is aligned.
3. Turn the cell until a continuous beep on the buzzer and a steady red led are obtained.
Red led status
Slow blinking
Rapid blinking
Constant on
Note:
if there is no signal, the buzzer beeps once per seconds.
4. Switch to the next cell by pushing the "SELECT" button of the Master module, the blinking red led
and the beeps indicate the number of the cell to align.
Turn the cell until a continuous beep on the buzzer and a steady red led are obtained.
5. To leave alignment mode, push and hold the "SELECT" button of the Master module for than 2
seconds until the buzzer beeps twice.
Switch 5:
Operating mode
ON
CHANNEL
MODE
1
2
3
4
5
ON
OFF
Barrier alignment
Buzzer status
Slow beep
Rapid beep
Continuous beep
DELAY
50
700
ms
Red light "ALARM":
Intrusion alarm
Alignment status
Poor
Good
Excellent
- 46 -
MIRIS 3000 / 3100
Setting the
response time

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Miris 3100

Table des Matières