Steam Supply Connections; Control Valves (Sakv******) Kits For Pressurized Steam Supplies; Fitting Kits (Sakr******) For Threaded Control Valves; Actuator Kits For Control Valves - Carel ultimateSAM Mode D'emploi

Masquer les pouces Voir aussi pour ultimateSAM:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.1 Control valves (SAKV******) kits for
pressurized steam supplies
A control valve is needed to regulate the flow of pressurized steam to an
ultimateSAM distributor. Actuators for the control valve are sold separately.
If a valve and actuator kit was not ordered with the ultimateSAM distributor,
refer to the design manual for information on how to size and select a
control valves and actuators. Information on actuators is provided in section
4.2. The codes for valve kits are shown in table 4.a.
SAKV
0
2
1
ID prefix
0
0
Material
F = Cast iron
S = Stainless steel
0 = Brass body with stainless steel (only for North America)
Operating
F = 0.1-4 bars (1.45-50psi )
pressure
Nominal size
A= 0.4
Kv (EU)
B= 0.63 (EU) B= 0.75 (North America)
Cv (US)
C= 1
D= 1.6 (EU) D=1.8 (North America)
E= 2.5 (EU) E = 2.9 (North America)
F= 4 (EU) F= 4.4 (North America)
G= 6.3
H= 10
I= 16
J= 25 (EU) J=24 (North America)
K= 40
L= 63 (Not available in North American market)
Region
U = North America
0 = Other
---
---
Specifics regarding the inlet connection on available control valves are
shown in Table 4.b.
Inlet-Outlet Connections
Material, Pressure, Region Codes
Valve Size
*****FH*0* - *****SF*0*
SAKV0**C*0
Flange DN 15
SAKV0**D*0
Flange DN 15
SAKV0**E*0
Flange DN 15
SAKV0**F*0
Flange DN 15
SAKV0**G*0
Flange DN 20
SAKV0**H*0
Flange DN 25
SAKV0**I*0
Flange DN 32
SAKV0**J*0
Flange DN 40
SAKV0**K*0
Flange DN 50
SAKV0**L*0
Flange DN 65
If the inlet pressure to the control valve is greater than 0.7 bar (10 psig),
the valve may generate significant noise due to the near sonic velocity of
the steam. (See section 6.1 of the design manual for more information.)
Because the noise and coincident vibration may shorten valve life, frequent
inspections of the valve may be required.
For information about the weight, dimensions, construction materials, and
rangeability of each valve, see the "Technical specifications" manual.

4. STEAM SUPPLY CONNECTIONS

x
x
x
x 0
3
4
5
6
7
Tab. 4.a
*****0F*U*
½" NPT Fem.
½" NPT Fem.
½" NPT Fem.
½" NPT Fem.
¾" NPT Fem.
1" NPT Fem.
1¼" NPT Fem.
1½" NPT Fem.
2" NPT Fem.
not available
Tab. 4.b
4.2 Fitting kits (SAKR******) for threaded
control valves
Note: For flanged control valves, the installer must provide the
appropriate fittings and piping to connect the valve to the
ultimateSAM distributor. For control valves having threaded connections,
optional fitting kits are available to facilitate the connection of the valve to both
the distributor inlet and the steam traps and strainers (section 4.3). The codes for
the fitting kits are shown in table 4.c.
SAKR
1
Prefix
0
0
Material
F = cast iron S =stainless steel
Size
24= ½"
Tube
44= 1"
Tube
64= 1 ½" Tube
Market
U = North America
---
---
Both iron and stainless steel fitting kits for the North American region have
NPT threads. The list of threaded pipe fittings provided in each kit is shown
in table 4.d.
Fitting List for SAKR0***U0
Pipe Size
Bushing
(NPT)
F-M (size)
******24**
2 (½"x1")
******34**
2 (¾"x1")
******44**
n/a
******54**
2 (1¼"x2")
******64**
2 (1½"x2")
******84**
n/a
4.3 Actuator Kit for control valves
Each control valve needs an actuator to control its motion. The system for
identifying actuator kits is shown in Table 4.e. Note: Not all of the possible
combinations shown on the table are available. Tables 4.f and 4.g indicate
which electronic or pneumatic actuator can be paired with which control
valve.
SAKA
1
ID prefix
0
0
E = Electronic
Type:
Identifier:
01 Sequential # - 02 - ---
Region:
U = North America
---
---
Electronic actuator selection
Valve Size
*****FH*0*
(Europe)
SAKV0**A*0
not available
SAKV0**B*0
SAKV0**C*0
SAKA0E0200
"SAKV0**D*0
SAKA0E0200
SAKV0**E*0
SAKV0**F*0
SAKA0E0200
SAKV0**G*0
SAKA0E0200
SAKV0**H*0
SAKA0E0200
SAKV0**I*0
SAKA0E0200
"SAKV0**J*0
SAKA0E0200
SAKV0**K*0
SAKV0**L*0
SAKA0E0200
Note: for valve types "*****FH*0*" the actuator is included in the
valve kit, so the code (SAKAE00200) indicated above is to be used
when ordering a spare actuator only.
19
"ultimateSAM - user" +03U0070EF - rel. 2.0 - 20150301
ENG
0
x
x x
U
0
3
4
2
5
6
34= ¾"
Tube
54= 1 ¼" Tube
84= 2"
Tube
3" Nipple
Union
M-M (size)
F-F (size)
2 (1/2")
1 (1")
2 (3/4")
1 (1")
2 (1")
1 (1")
2 (1 1/4")
1 (2")
2 (1 1/2")
1 (2")
2 (2")
1 (2")
0
x
x x
x
0
3
4
2
5
6
P = Pneumatic
0 = Others
Material, Region Codes
*****SF*0*
SAKV00F*U*
(Europe)
(North America)
not available
SAKA0E03U0
SAKA0E0300
SAKA0E03U0
SAKA0E0300
SAKA0E03U0
SAKA0E0300
SAKA0E03U0
SAKA0E0300
SAKA0E03U0
SAKA0E0300
SAKA0E03U0
SAKA0E0300
SAKA0E04U0
SAKA0E0300
SAKA0E04U0
SAKA0E0300
not available
Tab. 4.c
Tab. 4.d
Tab. 4.e
Tab. 4.f

Publicité

Chapitres

Table des Matières
loading