Electrical installation

3

Installation according to EMC requirements

Stop!
Control cables and mains cables must be separated from the motor cable to avoid
interferences.
0
Function module (option)
1
Star or delta connection as indicated on the motor nameplate
2
EMC-cable connector (not included in the delivery package)
3
Shielded motor cable, low-capacity (core/core ≤ 75 pF/m; core/shield ≤ 150 pF/m)
4
Connect the cable screen to PE with a surface as large as possible (PES). Use enclosed clamps.
5
Control cable (optionally)
6
Mounting plate with electrically conductive surface
EMC
Compliance with EN 61800-3/A11
Noise emission
Noise emission
Compliance with limit value classes A and B to EN 55011
E82EVxxxKxB00x
E82EVxxxKxB20x
12
A
Abb. 1-8
F
G
without additional measures
only by means of external filters
EDK82EV222 DE/EN/FR 6.0
B
D
C
E
M
3~
8200vec008