C0170
Configuration
v
TRIP reset
C0171
Delay for
auto-TRIP reset
C0182*
Integration time
S–ramps
C0183*
C0183
Diagnostics
Diagnostics
C0196*
Activation of
v
v
auto–DCB
auto DCB
L
Possible settings
Lenze
Choice
-0-
TRIP reset by mains switching,
-0-
s
, LOW–signal at X3/28, via
function module or communication
module
-1-
like -0- and additional auto TRIP
reset
-2-
TRIP reset through mains switching,
function module or communication
module.
-3-
TRIP reset by mains switching
0.00
0.00
0.00
0.00
0
No fault
102
TRIP active
104
Message "Overvoltage (
"Undervoltage (
142
Pulse inhibit
151
Quick stop active
161
DC-injection brake active
250
Warning active
-0-
-0-
Auto-DCB active if
output frequency < threshold C0019
-1-
Auto-DCB active if
output frequency < threshold C0019
and setpoint < threshold C0019
EDK82EV222 DE/EN/FR 6.0
Commissioning
Code table (excerpt)
{s}
60.00
{s}
50.00
O O O O U U U U
)" or
L L L L U U U U
)" active
7
IMPORTANT
TRIP reset via
l
function module or
communication
module with C0043,
module with C0043,
C0410/12 or C0135
bit 11.
bit 11.
Auto TRIP reset after
l
the time set under
C0171.
C0171.
C0182 = 0.00: Linear
l
ramp function
generator operation
C0182 > 0.00:
l
S-shaped ramp
function generator
(smooth)
Only display
Only display
53