Program 80 - Single solar power system and cylinder load from boiler
S1
min1
diff1
A1
S2
max1
Program 80: Pump A1 runs when:
S1 is greater than the threshold min1 and S1 is greater than S2 by the difference diff1
and S2 has not exceeded the threshold max1.
The feed pump A2 runs when:
S3 is greater than the threshold min2 and S3 is greater than S4 by the difference diff2
and S4 has not exceeded the threshold max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2
Program 81 (all programs +1):
The feed pump A2 runs when:
S3 is greater than the threshold min2 and S3 is greater than S2 by the difference diff2
and S2 has not exceeded the threshold max2.
A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2
All programs +2:
If sensor S2 has reached max1 (or if S4 has reached threshold max3 along with all programs +4),
pump A2 is switched on, and pump A1 keeps running. This provides a cooling function for the boiler /
heater without causing standstill temperatures in the collector.
All programs +4:
In addition, if S4 exceeds the threshold max3, pump A1 is switched off.
All programs +8: With re-cooling activated (all progr. +2) A3 runs concurrently.
A2
S3
S3
Required settings:
min2
max1 ... limit CYL S2
max2 ... limit CYL S4
diff2
max3 ... see all programs +4
A2
min1 ... switch-on temp. coll. S1
min2 ... switch-on temp. boiler S3
diff1
S4
diff2
max2
S4
S2
... coll. S1 – CYL S2
... boiler S3 – CYL S4
S1
A1
A1
A2
A1
A2
A1
A2
English
9