Assigned outputs
In the example, output 1 has been assigned to time window 1 (index). This output can be switched
between 6:30 AM and 9:30 PM.
The following outputs are assigned to the time window. (ex works = --)
A(AND) In the time window the respective program determines the status of the selected
OPA
outputs. Outside the time window they are switched off.
O (OR) The selected outputs are switched on in the time window. Outside the time
OPO
window the respective program determines the output status.
Setting range: combination of all outputs (such as OP 1, OP 23, OP 123)
The time at which the set outputs are allowed (ex works = 12:00 AM)
Setting range: 12:00 AM to 11:50 PM in increments of 10 min
The time at which the set outputs are blocked (ex works = 12:00 AM)
Setting range: 12:00 AM to 11:50 PM in increments of 10 min

Timer function TIMER

Setting the Timer function
The timer function can be assigned to any output.
It is possible to specify a release time (during this time the output is released) and a block time (during
this time the output is blocked). Release time and block time are active alternatively.
Assigned
outputs
28
Number of the time window
Release time
OPA 1 to OPA123 and OPO 1 bis OPO123
OP -- = no output (time window disabled)
Release time
Block time
Block time