In the example the timer function is assigned to output 1. The output is released for 5 hours and
blocked for 2 hours.
The timer function is assigned the following outputs. (ex works = --)
OPA A (AND) During the release time the respective program determines the status of the selected
outputs. During the block time they remain deactivated.
OPO O (OR) The selected outputs are released during the release time. During the block time the
respective program determines the output status.
Setting range : Combination of all outputs (e.g. OP 1, OP 23, OP 123)
Period for which the set outputs are enabled (ex works = 00:00)
Setting range:
Period for which the set outputs are disabled (es works = 00:00)
Setting range:
Assignment of free outputs A2/A3 <= OFF
Outputs which do not have a fixed assignment in the diagram (diagrams 0 to 159) can be linked to
other outputs.
A3 deactivated
A3 switches with A2
A3OFF Output A3 has no function
Output A3 is released and available as e.g. time switch output (setting: OPA 3)
A3ON
Output A3 switches together with output A1
A3A1
Output A3 switches together with output A2
A3A2
Output A3 switches if output A1 and output A2 have activated
A31U2
A3 = A1 & A2
Output A3 switches if output A1 or output A2 have activated.
A31O2
A3 = A1 oder A2
OPA 1 to OPA123 and OPO 1 to OPO123
OP -- = no output (timer function deactivated)
00:.00 to 23:50 in 10 min increments
00:00 to 23.50 in 10 min increments
A3 activated (as time
switch output)
A3 switches when
A1 and A2 are ON
A3 switches with A1
A3 switches when
A1 or A2 are ON