• Note of drainage raising pipe
Prepare a polyvinyl chloride pipe with a 32 mm outer diameter. Fasten the pipe to drain hose with the
adhesive agent and factory-supplied clamp. The drain pipe must be performed with a down-slope of
1/25 to 1/100.
Total length of a+b+c shall be within 1100 mm.
• Please install the drain hose according to the following process if several drain hoses join together.
2. Check the smoothness of drain after installation.
• Check the drain state by injecting 600cc water slowly from the outlet vent or test hole.
In case of pouring water through the test hole
• Check the drain in the state of refrigerating after installation of the electric circuit.
Note: Before obtaining access to terminals, all supply circuits must be disconnected.
Hose band
(Accessory)
c (50 Max.)
a (300 Max.)
1/25 to 1/100
down-slope
Drain hose (Accessory)
1/25 to 1/100 down-slope
Common drain piping
Insert the end of hose
between heat exchanger
and drain pan.
Test hole
Pump
Water
Hose band
Drain hose
(Accessory)
connection
15
Drain pipe
connection
This drain pipe shall be separated from other pipes.
Insert the end of hose
between heat exchanger
and drain pan.
In case of pouring water through the outlet vent
31
Polyvinyl chloride VP25
Drain hose
(Field supplied)
(Accessory)
Dain pan
Pump
Water