EtherNet/IP configuration
This web page is used to configure all the parameters relevant to the EtherNet/IP protocol standard.
Fig. 6
Real Time Ethernet Protocol Configuration - EtherNet/IP
Object
Description
Configuration of the static IP address if a DHCP server is not used. EtherNet/IP is not
IP Address
allowed to share the IP address with a CIM 500 webserver.
Subnet Mask
Configuration of the subnet mask if a DHCP server is not used.
Gateway
Configuration of the gateway address if a DHCP server is not used.
The CIM 500 module can be configured to automatically obtain its EtherNet/IP network
Use DHCP
settings from a DHCP
For enabling of a 5 seconds communication watchdog timer. Only active for pump or
booster products.
Communication
Unchecked: Watchdog is disabled (default)
Watchdog
Checked: Watchdog is enabled, time-out 5 seconds.
Watchdog action: The pump or the booster is set to local mode.
The module can be put in product simulation mode to generate realistic simulated
values of all the EtherNet/IP input data. It will thus be possible to connect a EtherNet/IP
master to a module fitted in a CIU or an E-box without installing this device in a real
Grundfos pro-
industrial process system. In an office environment, it can then be verified that commu-
duct simulation
nication
application program (for example PLC program) before installing the device.
To enable product simulation, select a product type from the dropdown list.
To terminate product simulation, select "No Simulation".
22
server,
if available on the network. Default: No use of DHCP.
works,
and data is received and handled correctly by the EtherNet/IP master