Electrical Connection Terminal Connection; Voltage Supply - IFM Electronic ecomot200 DS2005 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Mounting
Mount the unit on a DIN rail or by means of a mounting base. Leave enough
space between the unit and the top and bottom of the control cabinet to enable
air circulation to avoid excessive heating.
Take the internal heating of all units into account when mounting several units
side by side. The environmental conditions must be observed for every unit.
Mounting of the sensors:
Adhere to the mounting instructions of the manufacturer.
6. Electrical connection
Terminal connection
Monitor FS-2
AC/DC or
7 8
5
Sensor
supply
6
4
pnp
In 1
10
npn
11
pnp
In 2
12
npn
17
pnp
Release 1/2
Reset 1/2
18
pnp
Voltage supply (power)
It is only allowed to operate the unit via one of the possible voltage connections,
i.e. either terminals 7/8, AC/DC or terminals 1/2, 24 V DC.
The supply cable must be protected externally according to the cross-section used
(max. 16 A).
The terminals of the DC supply are directly connected to the terminals of the sen-
sor supply. The SELV criteria must therefore be met for the DC supply (safe extra-
low voltage, circuit galvanically separated from other circuits, not grounded).
Power
DC
1 2
3
16
Out 1
15
13
14
24
Out 2
21
19
20
Monitor FS-2N
Power
AC/DC or DC
7 8
1 2
Sensor
5
supply
I<0,1mA
In 1
I>6,0mA
Sensor
6
supply
11
Sensor
supply
I<0,1mA
In 2
I>6,0mA
12
Sensor supply
17
pnp
Release 1/2
Reset 1/2
18
pnp
FS-2 / FS-2N
MONITOR
3
4
16
Out 1
15
13
14
10
24
Out 2
21
19
20
23
PAGE

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ecomot200 ds2105

Table des Matières