System parameters

Parameter Description, values, default value
FOx
Function Output (switching function of the outputs 1 and 2)
F1
The relay is de-energised in case of slip and during the start-up delay STP.
(+ signal on terminal 17 = relay energised)
F2
The relay is energised in case of slip and during the start-up delay STP.
(+ signal on terminal 17 = relay de-energised)
F3
The relay is de-energised in case of synchronous running and during the start-up delay STP.
(+ signal on terminal 17 = relay de-energised)
F4
The relay is energised in case of synchronous running and during the start-up delay STP.
The relay is de-energised in case of slip (i.e. number of differential pulses > SPx)
(+ signal on terminal 17 = relay energised)
• Values: 1 ... 4
• Default value: 4 (operation for slip monitoring)
CTx
Cycle Time (reset time)
Time after which the corresponding differential pulse counter is reset.
The time starts on the first pulse edge at In1 or In2.
(See the "Operating principle" on page 21)
• Values: 0.0 ... 1000.0 s
• Default value: 0.0
NCx
Number of Cams (number of the switching cams)
Allows the indication of the rotational speed in RPM if there is more than one switching
cam per revolution.
It is also possible to compensate for a different number of cams between the pulse
pick-ups (drive/power take-off).
• Values: 1 ... 999
• Default value: 1 (highest setting sensitivity even if there are several cams,
the indicated value shows pulses/min, not RPM or Hz)
STP
Start-up Delay Time Parallel (start-up delay outputs 1/2)
Normally the output relays are energised after power on of the monitor FS-2 until the
drive is switched on.
The outputs then switch depending on the switching function and state of the plant.
The parameter applies to both outputs. It can be used to compensate for a slipping start
of the plant until synchronous running is achieved.
Monitoring starts on the first pulse edge after this time has elapsed.
The start-up delay can also be released externally while the monitor FS-2 remains
connected (see "Electrical connection").
• Values: 0.0 ... 1000.0 s (min. setting = 0.1 s)
• Default value: 0.0
FWx
Function Wire Break (wire monitoring, only FS-2N)
Relay action in case of a wire fault
if
FOx = 1
FOx = 2/3
FOx = 4
(default value)
• Values: 0 = inactive / 1 = active
• Default value: 0
FWx = inactive (0)
relay remains energised
relay remains de-energised
relay remains energised
MONITOR
FWx = active (1)
relay is de-energised
relay is de-energised
FS-2 / FS-2N
27