FS-2 / FS-2N
MONITOR
SOP
Store Output Parallel (latching function outputs 1/2
If the parameter is active, the outputs do not switch back automatically in case of a fault.
They must be reset internally or externally.
The function is simultaneously activated for both outputs.
The reset function is also effective for both outputs.
• Values: 0 = inactive / 1 = active front reset / 2 = front and external reset
• Default value: 0
OPP
Output Parallel (simultaneous switching of the outputs 1/2)
Determines whether the outputs switch simultaneously in case of a fault.
Independent of whether the number of differential pulses SP1 or SP2 was exceeded.
• Values: 0 = inactive / 1 = active (only effective if SOP active; 1 or 2 and FOx = 4)
• Default value: 0
DIM
Dimension (display format)
Indication in Hz or RPM (revolutions per minute)
• Values: 0 = RPM / 1 = Hz
• Default value: 0
VER
Software version
Possibility to look at the installed software version
(5-digit number with the abbreviation VCO)

Application parameters

Parameter Description, values, default value
SPx
Switch Point (switch point, number of the max. differential pulses)
Number of the differential pulses which must not be reached within the reset time
(e.g. SPx = 5, the relay is de-energised when the 5th differential pulse is reached).
The hysteresis (low switch point) is fixed to 2 differential pulses. It can only become
effective if the reset time CTx = 0.0 s.
• Values: 1 ... 999
• Default value: 1
DTx
Delay Time (delay time)
Enables a delayed switching of the outputs 1/2.
In case of a value greater than 0.0 the outputs only switch if the state of being above or
below the switch point is longer than the time set.
If e.g. for DTx = 5 s the allowed number of differential pulses is exceeded but is already
below this value after 3 s, the output does not switch.
• Values: 0.0 ... 1000.0 s (only effective if SOP inactive, 0)
• Default value: 0.0 (no delay time)
FTx
Fleeting Time (fleeting function)
If an event occurs, the output changes its state during the set time and then switches
back to the initial state.
• Values: 0.0 ... 1000.0 s
• Default value: 0.0 (fleeting time not active)